G G e e n n e e r r a a l l I I n n f f o o r r m m a a t t i i o o n n
provided for field installation on the entering water
side of the coil.

Boilerless Control/Electric Heat

(Option)
This option targets building designs that do not
incorporate a boiler to heat the loop system. During a
heavy heating load, the loop temperature may begin to
fall. As the loop temperature decreases, the heating
capacity of the heat pump will also decrease. In the
heating mode, when the loop temperature falls below
55°F (factory setting), the electric heater is energized,
and the compressor is locked out. The system's electric
heat source will continue to be utilized for primary
heating until the loop temperature rises above 60°F.
Once the loop temperature rises above 60°F, the
boilerless controller returns the unit to normal
compressor heating operation and locks out the electric
heater.
For the EXV and DXV models, the electric heat can be
factory installed or field installed by the contractor.
For the EXH and DXH models, the internal electric heat
must be factory installed, the external electric heat
must be field installed by the contractor.
N N o o t t e e : : Note: The boilerless controller has a field
adjustable entering water temperature setting of
25, 35, 45, 55, and 60 degrees. The compressor
operation will return to normal operation when
the loop temperature rises 5 degrees above the
setpoint.
Table 2. Refrigerant charge (EXH/EXV)
Heat Pump (oz)/
Model (60 Hz)
25.3 / 0.717
EXHF006
26.0 / 0.737
EXHF009
28.5 / 0.808
EXHF012
29.0 / 0.822
EXHF015
45.0 / 1.276
EXHF018
50.5 / 1.432
EXHF024
53.0 / 1.503
EXHF030
10
Heat Pump w/
Kg)
HGR (oz)/Kg)
26.8 / 0.760
27.5 / 0.780
30.5 / 0.865
30.5 / 0.865
48.0 / 1.361
53.0 / 1.503
56.0 / 1.588
Table 2. Refrigerant charge (EXH/EXV) (continued)
Heat Pump (oz)/
Model (60 Hz)
70.0 / 1.984
EXHF036
81.0 / 2.296
EXHF042
83.0 / 2.353
EXHF048
114.0 / 3.232
EXHF060
122.0 / 3.459
EXHF070
35 / 0.992
EXVG009
35 / 0.992
EXVG012
39.5 / 1.12
EXVG015
56 / 1.588
EXVG018
60 / 1.701
EXVG024
67 / 1.899
EXVG030
68 / 1.928
EXVG036
83 / 2.353
EXVG042
87 / 2.466
EXVG048
101 / 2.863
EXVG060
122 / 3.459
EXVG070
Table 3. Refrigerant charge (DXH/DXV)
Heat Pump (oz)/
Model (60 Hz)
54.5 / 1.545
DXHF024
71 / 2.013
DXHF036
89 / 2.523
DXHF048
106 / 3.005
DXHF060
118 / 3.345
DXHF070
59 / 1.673
DXVG024
64 / 1.814
DXVG036
86 / 2.438
DXVG048
101 / 2.863
DXVG060
123 / 3.487
DXVG070
Heat Pump w/
Kg)
HGR (oz)/Kg)
73.0 / 2.070
85.5 / 2.424
87.5 / 2.481
118.5 / 3.359
127.0 / 3.600
37 / 1.049
37 / 1.049
42.5 / 1.205
59.5 / 1.687
64 / 1.814
72.5 / 2.055
74 / 2.098
90.5 / 2.566
95 / 2.693
111 / 3.147
132 / 3.742
Heat Pump w/
Kg)
HGR (oz)/Kg)
————
————
————
————
————
63 / 1.786
70 / 1.984
94 / 2.665
111 / 3.147
133 / 3.77