Address Setting; Group Address - Toshiba RAV-RM301KRTP Series Service Manual

High wall type
Table of Contents

Advertisement

11-3. Address Setting

When determining indoor unit addresses with wiring completed without piping construction
Wiring example of 2 refrigerant systems
(Solid line: wiring, broken line: refrigerant piping)
O/U
(Power cable only)
I/U
I/U
Refrigerant line
1
1
address
Indoor unit address
1
2

Group address

1
2
For systems like this example, connect
a wired remote controller independently
without connecting remote controller wires,
and then set these addresses.
Group address
Individual: 0000
Header unit: 0001
in case of group control
Follower unit: 0002
SET DATA
SETTING
UNIT No.
R. C.
FILTER
RE S E T
TE ST
S E T
CL
8, 5, 2
4,
3, 6, 9
7,
10
11 1
END
Operation procedure
1
2
3
4
8
9
10
O/U
Refrigerant
line address →
(Power cable only)
I/U
I/U
I/U
Indoor unit
1
2
2
address →
3
1
2
2
2
2
Group
address →
CODE No.
N o.
O N / OFF
AN
M O D E
VE
VENT
S WIN G/ FI X
U NIT L OU VE R
5
6
7
11
END
(Manual setting by remote controller)
<Address setting procedure>
• Connect a remote controller to the indoor unit whose
address you want to set one to one.
• Turn ON the power.
1
Push
TEST
,
SET
, and
simultaneously for 4 seconds or more.
2

Set code
with
3
Set a refrigerant line address with
buttons.
4
Push
S E T
Indication on the LCD shows normal
operation.
5
!
Set code
with
6
Set indoor unit addresses with
tons.
7
S E T
Push
Indication on the LCD shows normal
operation.
8
"
Set code
with
9
Set indoor unit addresses with
as follows:
0000
Individual=
0002
unit=
10
Push
S E T
Indication on the LCD shows
normal operation.
11
Push
TE ST
.
Indoor unit address setting is completed.
The operation mode returns to normal OFF.
- 85 -
FILE NO. SVM-18059
CL
on the remote controller
TEMP.
buttons.
TIME
buttons.
TEMP.
TIME
but-
buttons.
TEMP.
TIME
buttons
0001