Toshiba RAV-RM301KRTP Series Service Manual page 61

High wall type
Table of Contents

Advertisement

H1 Readout of the setup data from EEPRO
(Data in EEPROM contents, which have been changed at the local site, are read out together with data in
EEPROM set at shipment from the factory.)
1. Push
,
∗ When group operation, the header indoor unit address is displayed at the first time. In this time, the CODE

No. (DN)
is displayed.
The fan of the second indoor unit operates and the louver starts swinging if any.
2. Every pushing [Unit, Louver
Specify the indoor unit No. to be replaced.
4. First change the CODE No. (DN) from
Make a note of the SET DATA displayed in this time.
5. Next change the CODE No. (DN) using the set temperature
Also make a note of the SET DATA.
6. Repeat item 5. and made a note of the important SET DATA as shown in the below table.

))
to
are provided in the CODE No. (DN). On the way of operation, CODE No. (DN) may skip.
7. After finishing making a note, push
(Approx. 1 minute is required to be able to use the remote controller.)
3
TIMER S E T
4
FILTER
RE S E T
TE ST
S E T
buttons of the remote controller at the same time for 4 seconds or more.
] button, the indoor unit address in the group are displayed successively.
/
buttons, the CODE No. (DN) can be moved up and down one by one.

to
TE ST
R.C. No.
O N / O F F
TIME
S AV E
CL

. (Setting of filter sign lighting time)
/
Minimum requirements for CODE No.
CODE No. (DN)
2
Capacity of the indoor unit is necessary to set
1
the revolutions of the fan.
- 61 -
FILE NO. SVM-18059
1
buttons.
4
Contents
11
Indoor unit capacity
12
Refrigerant line address
13
Indoor unit address
14
2
3