TEST EQUIPMENT

Turn on power to the system.
Fan Operation
If your system does not have a G terminal connection, skip to Heating System.
1.) Move fan switch to On position. The blower should begin to operate.
2.) Move fan switch to Auto position. The blower should stop immediately.
Heating System
1.) Move System Switch to Heat position. If the auxiliary heating system has a standing pilot,
be sure to light it.
2.) Press
to adjust thermostat setting to 1° above room temperature. The heat pump
system should begin to operate and the thermostat will indicate Heat On.
3.) Press
to adjust thermostat setting to 3° above room temperature. The auxiliary heat
should begin to operate and the thermostat will indicate Heat On Auxiliary.
4.) Press
to adjust thermostat setting 1° below room temperature. The heating system
should stop operating and the thermostat should indicate Heat.
Auxiliary System
1.) Move System Switch to Aux position. If the auxiliary heating system has a standing pilot,
be sure to light it.
2.) Press
to adjust thermostat setting to 1° above room temperature. The auxiliary heating
system should begin to operate and the thermostat will indicate Heat On Auxiliary.
3.) Press
to adjust thermostat setting 1° below room temperature. The auxiliary heating
system should stop operating and the thermostat should indicate Heat Auxiliary.
Cooling System
1.) Move System Switch to Cool position.
2.) Press
to adjust thermostat setting 1° below room temperature. The blower should
come on immediately on high speed, followed by cold air circulation. The thermostat will
indicate Cool On. There can be up to a 5 minute delay. (see INSTALLER MENU, item 50)
3.) Press
to adjust thermostat setting to 1° above room temperature. The cooling system
should stop operating and the thermostat will indicate Cool.
Note: If Starting Soon is shown on the display, the compressor lockout feature is operating.
There will be up to a 5 minute delay before the compressor turns on.(see INSTALLER MENU,
item 50)
To prevent compressor and/or property damage, if the outdoor temperature is below 50°F,
Do not allow the compressor to run unless the compressor oil heaters have been operational
for 6 hours and the system has not been operational for at least 5 minutes.
4
Description
Fahrenheit or Celsius
Temperature Display Adjustment
(adjust the displayed "Room
Temperature")
Continuous Display Light (keep
the backlight always on – "C" wire
required)
Change Air Filter (set up a monthly
reminder)
Keypad Lock (prevent unwanted
changes to the thermostat)
DO NOT operate the cooling system.
Default Setting
(flashing icons)
CAUTION
!
Settings
(Press
°F – Fahrenheit
°F
°C – Celsius
0
-5 to +5
On – always on
OFF
OFF – momentarily
1 to 12 – reminder time
OFF
OFF – no filter reminder
On – disable buttons
OFF
OFF – all buttons are active
or
)
(months)