6.3.4.9
Low Air Multiplier
Adjusts the airflow speed on non- - communicating two- - stage units. Choose 0.65 for
units with a Bristol compressor, choose 0.80 (default) for units with a Copeland
scroll compressor.
6.3.4.10.
Energy Efficiency
This option is used to input the published ratings of the installed air conditioner or
heat pump as part of the energy tracking calculation. After the ratings are entered,
touch SAVE.
6.3.5.

Heat Source Lockout

First touch SETUP, then touch HEAT SOURCE LOCKOUTS to set up the
parameters for the AC/Heat Pump unit.
For hydronic heat applications, this option allows the installer to set the lockout
temperatures below which only the hydronic coil will operate, and the lockout
temperature above which the hydronic coil will not operate. After the selections are
made, touch SAVE.
HP Lockout: Adjustable from - - 20 to 55_F (- - 28 to 13_C) or None
S
Default = None
d
Furnace, Electric Heat or Hydronic Lockout: Adjustable from 15 to 55_F
S
52
A12149