Failures With No Error Code - Fujitsu WATERSTAGE WOYG160LJL Maintenance Document

Air to water heat pump split single service and integrated dhw type
Hide thumbs Also See for WATERSTAGE WOYG160LJL:
Table of Contents

Advertisement

▼ Failures With No Error Code

Clear 35: No voltage on Hydraulic Unit
Probable causes:
• Power supply fault.
• External causes.
• Faulty electrical components.
Check:
2. Check for external causes on the Hydraulic Unit and outdoor unit (noise or voltage drop):
-
Check for any other electrical device on the same electric circuit which might cause a drop in
voltage.
-
Check for any current leaks.
-
Check for any equipment generating electromagnetic waves which interfere with the
communication between the Hydraulic Unit and the outdoor unit.
3. Check the electrical components:
-
Check that a voltage between AC 198 and AC 264 V exists between terminals 1 and 2 on the
Hydraulic Unit terminal block.
-
Check Interface PCB for :
either the fuse (F1).
o
or the varistor (VA1). Fault: overvoltage - external causes - power supply to be
o
checked).
-
Replace the faulty component (if the varistor is blown, the PCB must be replaced).
If all of these checks are unsuccessful, replace Interface PCB.
Waterstage / Maintenance Manual / 2105 - EN
1. Check the installation :
- Is the circuit breaker cut off?
- Check the wiring.
- 33 -