Airstream TC5-2V4SA User Manual page 32

Table of Contents

Advertisement

TC5-2V4SA
Table 1.
STAGE 6
OPERATION
Cooling
Heating
Interaction Between Temperature and Minimum Speed
Curves
The minimum speed curve can be activated only if the tempera-
ture curve is already activated
All points of the minimum speed curve other than the first one are
automatically given day numbers identical to those specified for the tem-
perature curve. Only the first point of the minimum speed curve has an
adjustable day number. This day number must be greater or equal to the
day number specified for the first point of the temperature curve and less
than the day number specified for the second point of the temperature
curve (see example 1).
32
TC5-2V4SA rev.06
''Set Point - 5.0°F (2.8°C) - Heater Offset - Stage 6 Differential''
''Set Point'', if the parameter settings are such that the pre-
ceding value is greater than the set point.
THRESHOLD VALUE
''Set Point - 5.0°F (2.8°C)''
OR