Download Print this page

Advertisement

Quick Links

Si01-983
REMOVAL
PROCEDURE
S E R V I C E
M A N U A L
12000/18000 Btu/h Class
Outdoor Unit
Non-Inverter
Pair Type

Advertisement

loading

Summary of Contents for Daikin RE12JV2S

  • Page 1 Si01-983 REMOVAL PROCEDURE S E R V I C E M A N U A L 12000/18000 Btu/h Class Outdoor Unit Non-Inverter Pair Type...
  • Page 2 Service Manual Removal Procedure Outdoor Unit Cooling Only RE12JV2S RE18JV2S...
  • Page 3: Table Of Contents

    Si01-983 Table of Contents 1. Removal of Outer Panels / Fan Motor.............2 2. Removal of Electrical Components ............10 3. Removal of Sound Blankets..............14 4. Removal of Capillary Tube (Pattern 1)..........15 5. Removal of Capillary Tube (Pattern 2)..........16 6. Removal of Compressor ASSY.............17 Note: The illustrations may be slightly different depending on the model.
  • Page 4: Removal Of Outer Panels / Fan Motor

    Removal of Outer Panels / Fan Motor Si01-983 1. Removal of Outer Panels / Fan Motor Procedure Warning Be sure to wait for 10 minutes or more after turning off all power supplies before disassembling work. Step Procedure Points 1. Appearance features (R15226) Take care not to cut your finger by the fins of the...
  • Page 5 Si01-983 Removal of Outer Panels / Fan Motor Step Procedure Points Remove the 3 screws and remove the top Top panel panel. (R15227) Remove the 4 screws and remove the discharge grille. (R15257) The discharge grille has 4 hooks. (R16411) Removal Procedure...
  • Page 6 Removal of Outer Panels / Fan Motor Si01-983 Step Procedure Points Remove the 8 screws and remove the front panel. (R15228) Front panel Unfasten the hooks. The front panel has 4 hooks. Pull and remove the front panel. Hook (R16412) Removal Procedure...
  • Page 7 Si01-983 Removal of Outer Panels / Fan Motor Step Procedure Points 3. Remove the fan motor. Nut size: M6 Remove the nut of the outdoor fan. 10 mm (R12236) Outdoor fan (R15230) Remove the outdoor Align the mark of the fan.
  • Page 8 Removal of Outer Panels / Fan Motor Si01-983 Step Procedure Points Remove the screw and Put the fan motor lead wire remove the fan motor through the back of the fan fixing frame. motor when reassembling so as not to be entangled with the outdoor fan.
  • Page 9 Si01-983 Removal of Outer Panels / Fan Motor Step Procedure Points Release the fan motor lead wire from the hooks. (R15234) Remove the 4 screws and remove the fan motor. motor (R15235) Removal Procedure...
  • Page 10 Removal of Outer Panels / Fan Motor Si01-983 Step Procedure Points 4. Remove the right side panel. Remove the 3 screws and disconnect the connecting wire. Remove the screw and remove the wire clamp. Connecting wire Wire (R15377) clamp Lift up and remove the guard net.
  • Page 11 Si01-983 Removal of Outer Panels / Fan Motor Step Procedure Points Remove the 4 screws on the right side. Right side panel (R15238) Remove the screw near the connection port. (R15239) Unfasten the hook of When reassembling, make the right side panel. sure to fit the hook.
  • Page 12: Removal Of Electrical Components

    Removal of Electrical Components Si01-983 2. Removal of Electrical Components Procedure Warning Be sure to for wait for 10 minutes or more after turning off all power supplies before disassembling work. Step Procedure Points Remove the nut and Preparation remove the terminal Remove the outer panels cover.
  • Page 13 Si01-983 Removal of Electrical Components Step Procedure Points The layout of the Pattern 1 electrical components and connectors is different by models. X11A (R10848) X11A (R10849) White X1M(1): red X1M(2):black X1M(1) Compressor(S): yellow Compressor(R): red X11A (R10850) (R10851) Compressor(C): blue Upper Lower X11A: black...
  • Page 14 Removal of Electrical Components Si01-983 Step Procedure Points Pattern 2 X11A (R10853) X11A (R10854) K1M(4): red Compressor (R) Compressor (S) : red : yellow (R10855) REC: white REC: white K1M(6): black white X11A (R10856) Removal Procedure...
  • Page 15 Si01-983 Removal of Electrical Components Step Procedure Points X2M(N): white C2: white K1M(A2): black K1M(A1): black X1M(2): white (R10857) K1M(3): black REC: white K1M(1): red X2M(N): black Upper Lower X2M(L): red X1M(2) X1M(3) SECT. A-A X2M(GRD) X1M(1) : green / yellow Earth: green / yellow 1 2 3 X1M(GRD)
  • Page 16: Removal Of Sound Blankets

    Removal of Sound Blankets Si01-983 3. Removal of Sound Blankets Procedure Warning Be sure to wait for 10 minutes or more after turning off all power supplies before disassembling work. Step Procedure Points Remove the sound Preparation blanket (top). Remove the outer panels Sound according to the “Removal of Untie the 2 strings and...
  • Page 17: Removal Of Capillary Tube (Pattern 1)

    Si01-983 Removal of Capillary Tube (Pattern 1) 4. Removal of Capillary Tube (Pattern 1) Procedure Warning Be sure to wait for 10 minutes or more after turning off all power supplies before disassembling work. Step Procedure Points Before working, make sure that the refrigerant Warning gas is empty in the circuit.
  • Page 18: Removal Of Capillary Tube (Pattern 2)

    Removal of Capillary Tube (Pattern 2) Si01-983 5. Removal of Capillary Tube (Pattern 2) Procedure Warning Be sure to wait for 10 minutes or more after turning off all power supplies before disassembling work. Step Procedure Points Before working, make sure that the refrigerant Warning gas is empty in the circuit.
  • Page 19: Removal Of Compressor Assy

    Si01-983 Removal of Compressor ASSY 6. Removal of Compressor ASSY Procedure Warning Be sure to wait for 10 minutes or more after turning off all power supplies before disassembling work. Step Procedure Points Remove the nut and remove the terminal cover.
  • Page 20 Removal of Compressor ASSY Si01-983 Step Procedure Points Before working, make sure that the refrigerant Warning gas is empty in the circuit. Be careful not to get yourself Be sure to apply nitrogen burnt with the pipes and other Discharge side replacement when parts that are heated by the...
  • Page 21 Revision History Month / Year Version Revised contents 02 / 2013 Si01-983 First edition...
  • Page 22 Improper installation can result in water or refrigerant leakage, electrical shock, fire or explosion. Use only those parts and accessories supplied or specified by Daikin. Ask a qualified installer or contractor to install those parts and accessories. Use of unauthorised parts and accessories or improper installation of parts and accessories can result in water or refrigerant leakage, electrical shock, fire or explosion.