Fuses (Option +F260); Dimensions And Weights; Free Space Requirements; Losses, Internal Cooling Circuit Data And Noise - ABB ACS880-7407LC Hardware Manual

Semiconductor switch units
Table of Contents

Advertisement

58 Technical data

Fuses (option +F260)

ACS880-
7407LC-...
Quantity
0500A-7
1250A-7
3000A-7

Dimensions and weights

ACS880-
7407LC-...
0500A-7
1250A-7
3000A-7

Free space requirements

The values are as required by cooling, maintenance and/or operation of the pressure relief
(if present). Also obey the general mechanical installation instructions.
Front
mm
1500

Losses, internal cooling circuit data and noise

ACS880-
7407LC-...
P
loss total
kW
0500A-7
3.2
1250A-7
7.9
3000A-7
17.9
These losses are not calculated according to IEC 61800-9-2.

Terminal data for the control cables

Nom. voltage / current: 500 V / 17.5 A, connection method: spring-cage connection, cross
section: 0.08 mm² - 1.5 mm² (AWG: 28 - 16)
A
2
800
2
2000
2
5000
Height
Width
mm
2002
2002
2002
in.
mm
59
0
Losses
P
P
loss coolant
loss air
kW
kW
3.0
0.2
7.6
0.3
17.5
0.4
DC fuses
V
1250
Bussmann Eaton
1000
Bussmann Eaton
1000
Bussmann Eaton
Depth
mm
mm
600
644
600
644
600
644
Sides
in.
0
Cooling circuit data
Total
Massflow
l
l/min
5
5.5
6
Manufacturer
Type
170M6546
170M7608
170M7622
Weight
kg
325
378
440
Above
mm
250
9.85
Noise (Avg)
Pressure
loss
kPa
26
120.0
38
120.0
48
120.0
in.
dB(A)
63
63
63

Advertisement

Table of Contents
loading

Table of Contents