INVERTER INSTALLATION AND PRECAUTIONS

 Inverter model
r
FR -
F8 0
6
Symbol Voltage class
Symbol
00680 to 04420 Inverter SLD rated current (A)
6
600 V class
Capacity plate
Inverter model
Serial number
 Inverter placement
Installation on the enclosure
Fix six positions for the FR-F860-02890 or higher.
 Installation environment
Before installation, confirm that the following environment conditions are met.
Item
FR-F860-00680, 01080
Surrounding air
temperature

FR-F860-01440 or higher
Ambient
95% RH or less (non-condensing)
humidity
Storage
-20 to +65°C

temperature
Atmosphere
Indoors (free from corrosive gas, flammable gas, oil mist, dust and dirt)
Altitude
Maximum 2500 m.

2
Vibration
5.9 m/s
or less at 10 to 55 Hz (directions of X, Y, Z axes)


Temperature applicable for a short time, e.g. in transit.

For the installation at an altitude above 1000 m, consider a 3% reduction in the rated current per 500 m increase in altitude.
2

2.9 m/s
or less for the FR-F860-02890 or higher.

Surrounding air temperature is a temperature measured at a measurement position in an enclosure.
Ambient temperature is a temperature outside an enclosure.
-
00680
- 3
-
60
Description
• Install the inverter on a strong surface securely with screws.
• Leave enough clearances and take cooling measures.
• Avoid places where the inverter is subjected to direct sunlight, high temperature and high humidity.
• Install the inverter on a nonflammable wall surface.
• When encasing multiple inverters, install them in parallel as a cooling measure.
• When designing or building an enclosure for the inverter, carefully consider influencing factors such as heat
generation of the contained devices and the operating environment.
Allow clearance.

For replacing the cooling fan of the FR-F860-02890 or higher, 30 cm of space is necessary in front of the inverter.
Refer to the Instruction Manual (Detailed) for fan replacement.
-10°C to +40°C (non-freezing)
-10°C to +50°C (non-freezing) (LD rating)
-10°C to +40°C (non-freezing) (SLD rating)
Symbol Type
Symbol
(conforming to IEC60721-3-3 3C2/3S2)
3
CA3
60
06
Rating plate
Inverter model
Input rating
Output rating
SERIAL
Country of origin
Clearances (front)
FR-F860-01080 or lower
10 cm
or more
5 cm
or more
Vertical
10 cm
or more
Description
INVERTER INSTALLATION AND PRECAUTIONS
Circuit board coating
Plated
conductor
With
Without
With
With
FR-F860-01440 or higher
20 cm
or more
5 cm
or more
10 cm
10 cm
or more
or more
20 cm
or more
Enclosure
5 cm
Measurement
position
Clearances (side)
5 cm
or more
∗1
Inverter
Measurement
position
Inverter
5 cm
5 cm
5