1
INVERTER INSTALLATION AND PRECAUTIONS
Inverter model
FR -
Symbol Voltage class
2
200 V class
4
400 V class
Specification differs by the type. Major differences are shown in the table below.
Type
FM
(terminal FM equipped model)
CA
(terminal CA equipped model)
Conforming to IEC 60721-3-3 3C2/3S2
Applicable for the FR-A820-00340(5.5K) or higher, and the FR-A840-00170(5.5K) or higher.
Capacity plate
NOTE
• In this Instruction Manual, the inverter model name consists of the applicable motor capacity and the rated current. (Example) FR-A820-00046(0.4K)
Inverter placement
Installation on the enclosure
Fix six positions for the FR-A840-04320(160K) or higher.
Installation environment
Before installation, confirm that the following environment conditions are met.
LD, ND (initial setting), HD
Surrounding air
temperature
SLD
Ambient humidity
Storage temperature
Atmosphere
Altitude
Vibration
Temperature applicable for a short time, e.g. in transit.
For the installation at an altitude above 1000 m, consider a 3% reduction in the rated current per 500 m increase in altitude.
2.9 m/s
Surrounding air temperature is a temperature measured at a measurement position in an enclosure.
Ambient temperature is a temperature outside an enclosure.
For the amount of heat generated by the inverter unit, refer to the Instruction Manual (Detailed).
Downloaded from
ManualsNet.com
A8 0
2
-
00046
-
1
-
Symbol
Description
00023 to 06830
Inverter SLD rated current (A)
0.4 to 280K
Inverter ND rated capacity (kW)
Monitor output
Terminal FM: pulse train output
Terminal AM: analog voltage output (0 to 10 VDC)
Terminal CA: analog current output (0 to 20 mADC)
Terminal AM: analog voltage output (0 to 10 VDC)
FR-A820-00046-1-GN
Inverter model
Serial number
• Install the inverter on a strong surface securely with screws.
• Leave enough clearances and take cooling measures.
• Avoid places where the inverter is subjected to direct sunlight, high temperature and high humidity.
• Install the inverter on a nonflammable wall surface.
• When encasing multiple inverters, install them in parallel as a cooling measure.
• When designing or building an enclosure for the inverter, carefully consider influencing factors such as heat generation
of the contained devices and the operating environment.
Allow clearance.
Item
-10 to +50°C (non-freezing)
-10 to +40°C (non-freezing)
With circuit board coating (conforming to IEC 60721-3-3 3C2/3S2): 95% RH or less (non-
condensing),
Without circuit board coating: 90% RH or less (non-condensing)
-20 to +65°C
Indoors (free from corrosive gas, flammable gas, oil mist, dust and dirt)
2500 m or lower
2
5.9 m/s
or less at 10 to 55 Hz (directions of X, Y, Z axes)
2
or less for the FR-A840-04320(160K) or higher.
search engine
GN
Symbol Type
Symbol Circuit board coating
1
FM
None
2
CA
60
06
Built-in
EMC filter
OFF
ON
Rating plate
Inverter model
Input rating
Output rating
SERIAL
Country of origin
FR-A820-03160(55K) or lower,
FR-A840-01800(55K) or lower
10 cm
or more
5 cm
or more
∗1,∗2
Vertical
10 cm
or more
For the FR-A820-00250(3.7K) or lower and FR-A840-00126(3.7K) or lower, allow 1 cm or more clearance.
When using the FR-A820-01250(22K) or lower and FR-A840-00620(22K) or lower at the surrounding air temperature of
40°C or less (30°C or less for the SLD rated inverter), side-by-side installation (0 cm clearance) is available.
There needs to be a space of at least 30 cm in front of the inverter to replace the cooling fan of the FR-A840-04320(160K)
or higher.
Refer to the Instruction Manual (Detailed) for fan replacement.
INVERTER INSTALLATION AND PRECAUTIONS
Plated conductor
Symbol
GN
Without
Without
With
Without
With
With
Initial setting
Rated
Control logic
Pr.19 Base frequency voltage
frequency
9999
Sink logic
60 Hz
(same as the power supply voltage)
8888
Source logic
50 Hz
(95% of the power supply voltage)
Clearances (front)
FR-A820-03800(75K) or higher,
FR-A840-02160(75K) or higher
20 cm
or more
5 cm
10 cm
10 cm
or more
or more
or more
∗1,∗2
20 cm
or more
Description
Enclosure
5 cm
Measurement
position
Function
CC-Link IE TSN functionality
Clearances (side)
5 cm
or more
∗1,∗3
Inverter
Measurement
position
Inverter
5 cm
5 cm
3