Danger Bypass - GE Bently Nevada 3300/25 Operation Manual

Dual accelerometer input monitor
Table of Contents

Advertisement

1.
Open the front panel by loosening the two monitor retaining screws and sliding
the front panel to the right.
2.
Set DB (Danger Bypass) switch to the left (ON). Both channel BYPASS LEDs come
on. The DANGER LEDs on the front panel can come on, but the danger relay drive
will not be activated if a Danger setpoint is exceeded. The Danger Bypass switch
can only be turned on if Danger Bypass is enabled. To enable the Danger Bypass
switch refer to the Setting Field Programmable Options section of this manual.
3.
Close the front panel.

12. Danger Bypass

Caution
Machine protection provided by
this monitor will be lost while
Danger Bypass is on.
Section 12 - Danger Bypass
27