Electrical Data - Bryant 583A User Manual

Single-package gas heating/electric cooling units
Table of Contents

Advertisement

UNIT
SIZE
V-PH-Hz
583A
024
208/230-1-60
208/230-1-60
030
208/230-3-60
208/230-1-60
036
208/230-3-60
460-3-60
208/230-1-60
042
208/230-3-60
460-3-60
208/230-1-60
048
208/230-3-60
460-3-60
208/230-1-60
060
208/230-3-60
460-3-60
LEGEND
FLA
— Full Load Amps
HACR — Heating, Air Conditioning
and Refrigeration
LRA
— Locked Rotor Amps
MCA
— Minimum Circuit Amps
MOCP — Maximum Overcurrent Protection
RLA
— Rated Load Amps
*Fuse or HACR Breaker.
NOTES:
1. In compliance with NEC (National Electrical Code) requirements for
multimotor and combination load equipment (refer to NEC
Articles 430 and 440), the overcurrent protective device for the unit
shall be fuse or HACR breaker. The CGA (Canadian Gas
Association) units may be fuse or circuit breaker.
2. Minimum wire size is based on 60 C copper wire. If other than
60 C wire is used, or if length exceeds wire length in table,
determine size from NEC.
3. Unbalanced 3-Phase Supply Voltage
Never operate a motor where a phase imbalance in supply voltage is
greater than 2%. Use the following formula to determine the percent-
age of voltage imbalance.
% Voltage imbalance
max voltage deviation from average voltage
= 100 x
average voltage

ELECTRICAL DATA

VOLTAGE
COMPRESSOR
RANGE
Min
Max
RLA
187
253
10.3
187
253
13.5
187
253
9.0
187
253
16.7
187
253
11.2
414
506
5.4
187
253
17.9
187
253
12.4
414
506
6.1
187
253
19.5
187
253
12.4
414
506
5.8
187
253
28.8
187
253
17.3
414
506
9.0
OUTDOOR FAN
MOTOR
LRA
FLA
56.0
0.8
73.0
0.8
63.0
0.8
97.0
0.8
75.0
0.8
37.5
0.9
104.0
1.6
88.0
1.6
44.0
0.9
104.0
1.6
88.0
1.6
44.0
0.9
169.0
1.6
123.0
1.6
62.0
0.9
EXAMPLE: Supply voltage is 460-3-60.
Determine maximum deviation from average voltage.
(AB) 457 − 452 = 5 v
(BC) 464 − 457 = 7 v
(AC) 457 − 455 = 2 v
Maximum deviation is 7 v.
Determine percent of voltage imbalance.
% Voltage Imbalance = 100 x
This amount of phase imbalance is satisfactory as it is below the
maximum allowable 2%.
IMPORTANT: If the supply voltage phase imbalance is more than 2%,
contact your local electric utility company immediately.
20
INDOOR FAN
POWER SUPPLY FUSE OR
MOTOR
HACR BRKR
FLA
MCA
2.0
15.7
2.1
19.8
2.1
14.2
3.6
25.3
3.6
18.4
1.9
9.6
4.1
28.1
4.1
21.2
2.0
10.5
4.1
30.1
4.1
21.2
2.0
10.2
6.2
43.8
6.2
29.4
3.2
15.4
AB = 452 v
BC = 464 v
AC = 455 v
452
Average Voltage =
1371
=
3
= 457
7
457
= 1.53%
MOCP*
25
30
20
40
25
15
45
30
15
45
30
15
60
45
20
464
455
3