Requirements for Line Current Transformers
•
Relation between the maximum and minimum C.T. ratios in all the positions connected to the
same bus ................................................. 10 maximum
•
Minimum saturation voltage required for main C.T's (for IN = 5 amps)
•
Intermediate Current Transformers: Normal ratios 5/2-1.33-1-0.5-0.2. Other ratios, including
multiple ratios are available according to application.
•
Stabilization Resistance: 250 Ohms.
•
Restraint Percentage: Adjustable form 0.5 to 0.8 in 0.1 steps
•
Sensitivity: (for internal faults):
•
Operation time (output relay included): Below 10 milliseconds
•
Alarm Unit:
Operation threshold: 0.027 Amps.
Operation time: 10 Seconds.
•
Short-circuit link for coupling currents: operation time adjustable between 100 and 1600
milliseconds.
•
Line Trip Supervision Units (optional)
•
Independent Units: Operation threshold between 0.2 and 3.3 amps
•
Dependent units: Operation threshold between 25 and 100% of the breaker failure unit
adjustment.
•
Breaker failure units (optional):
Operation threshold between 0.2 and 3.3 amps
Reset time below 12 milliseconds
Discrimination time between 100 and 730 milliseconds
•
Infeed Source: 125 VDC. Amps systems consumption in mA.
Single bus system
Trip output (per position)
Supervision and breaker
Failure units (per position)
•
Trip contacts:
Make and carry for trip cycle (according to ANSI C37.90)........30 amps
Break: Resistive 180 VA at 125/250 VDC.
Break: Inductive 60 VA at 125/250 VDC.
•
Accuracy:
Operation current:
Operation time:
GEK-98514B
Adjustable form 0.2 to 2.0 amps
5%
5%
BUS1000 Busbar Protection
2. TECHNICAL SPECIFICATIONS
100 V
Normal
280
-
70
Tripped
670
65
140
2-3