GE BUS1000 Instructions Manual page 11

Bus bar protection
Table of Contents

Advertisement

Requirements for Line Current Transformers
Relation between the maximum and minimum C.T. ratios in all the positions connected to the
same bus ................................................. 10 maximum
Minimum saturation voltage required for main C.T's (for IN = 5 amps)
Intermediate Current Transformers: Normal ratios 5/2-1.33-1-0.5-0.2. Other ratios, including
multiple ratios are available according to application.
Stabilization Resistance: 250 Ohms.
Restraint Percentage: Adjustable form 0.5 to 0.8 in 0.1 steps
Sensitivity: (for internal faults):
Operation time (output relay included): Below 10 milliseconds
Alarm Unit:
Operation threshold: 0.027 Amps.
Operation time: 10 Seconds.
Short-circuit link for coupling currents: operation time adjustable between 100 and 1600
milliseconds.
Line Trip Supervision Units (optional)
Independent Units: Operation threshold between 0.2 and 3.3 amps
Dependent units: Operation threshold between 25 and 100% of the breaker failure unit
adjustment.
Breaker failure units (optional):
Operation threshold between 0.2 and 3.3 amps
Reset time below 12 milliseconds
Discrimination time between 100 and 730 milliseconds
Infeed Source: 125 VDC. Amps systems consumption in mA.
Single bus system
Trip output (per position)
Supervision and breaker
Failure units (per position)
Trip contacts:
Make and carry for trip cycle (according to ANSI C37.90)........30 amps
Break: Resistive 180 VA at 125/250 VDC.
Break: Inductive 60 VA at 125/250 VDC.
Accuracy:
Operation current:
Operation time:
GEK-98514B
Adjustable form 0.2 to 2.0 amps
5%
5%
BUS1000 Busbar Protection
2. TECHNICAL SPECIFICATIONS
100 V
Normal
280
-
70
Tripped
670
65
140
2-3