Selection Procedure - Bryant 574B User Manual

Single-packaged gas heating/electric cooling units
Table of Contents

Advertisement

I
DETERMINE COOLING AND HEATING REQUIREMENTS
AT DESIGN CONDITIONS:
Given:
Required Cooling Capacity (TC)....................... 34,500 Btuh
Sensible Heat Capacity (SHC)......................... 26,000 Btuh
Required Heating Capacity............................... 60,000 Btuh
Condenser Entering Air Temperature...........................95°F
Indoor-Air Temperature ........................80°F edb 67°F ewb
Evaporator Air Quantity .....................................1200 CFM
External Static Pressure....................................... 0.2 in. wg
Electrical Characteristics.......................................230-1-60
II
SELECT
UNIT
BASED
CAPACITY.
Enter Net Cooling Capacities table at condenser entering
temperature of 95 F. Unit 036 at 1225 cfm and 67 F ewb
(entering wet bulb) will provide a total capacity of 36,500
Btuh and a SHC of 27,600 Btuh. Calculate SHC correction,
if required, using Note 4 under Cooling Capacities tables.
III
SELECT HEATING CAPACITY OF UNIT TO PROVIDE
DESIGN CONDITION REQUIREMENT.
In the Heating Capacities and Efficiencies table on page 4,
note that the unit 036090 will provide 70,000 Btuh with an
input of 90,000 Btuh.
574B CORNER WEIGHTS
1
y
4
CORNER #
024
1
70
2
54
3
84
4
141
TOTAL WEIGHT
350
SELECTION PROCEDURE (WITH EXAMPLE)
ON
REQUIRED
COOLING
x
030
036
042
78
60
94
156
388
IV
DETERMINE FAN SPEED AND POWER REQUIRE-
MENTS AT DESIGN CONDITIONS.
Before entering the air delivery tables, calculate the total
static pressure required. From the given example, the Wet
Coil Pressure Drop Table, and the Filter Pressure Drop table
on page 16, find at 1200 cfm:
Wet Coil Pressure Drop
External Static Pressure
Filter Pressure Drop
Total Static Pressure
Enter the table for Dry Coil Air Delivery — Horizontal and
Downflow Discharge. At 0.362 ESP (external static
pressure), the fan will deliver 1235 cfm with the NOM Speed
pin selected.
V
SELECT UNIT THAT CORRESPONDS TO POWER
SOURCE AVAILABLE.
The Electrical Data table shows that the unit is designed to
operate at 208/230-1-60.
—12—
2
3
048
060
92
100
72
78
111
120
188
201
463
499
0.032 in. ws
0.2 in. wg
0.13 in. wg
0.362 in. wg