Vitoflex 300-RF Technical Data
Ecocontrol Accessories
Accessories for Ecocontrol remote transfer/remote monitoring
Fault message device, analogue with battery
4 different voice messages are possible, as the fault
message modem has 4 independent digital inputs.
Standard delivery:
Analogue modem for wall mounting
Rechargeable battery pack (also works in the event of
a power failure)
To be carried out by the customer:
Electrical connection of the phone line to the modem
Configuration in accordance with the documentation
External visualization (hardwired)
Package for the transmission of relevant data to an IT
workstation (internal and/or external) for visualisation,
remote maintenance and operating data archiving of the
Vitoflex 300-RF boiler system. Hardware and software are
integrated into the Ecocontrol control unit. All adjustable
parameters can be changed from the IT workstation.
Standard delivery:
Industrial PC with interfaces for screen, keyboard and
PC mouse for IT workstation close to boiler room
Windows operating system, remote maintenance
software and visualisation/archiving software installed
on the industrial PC
Images on the screen:
Cross-sectional image of boiler, 3D with display fields
Table of parameters (with change option)
To be carried out by the customer:
IT workstation for remote maintenance, installation of
remote maintenance software
(continued)
Controller module
For the function extension of the Ecocontrol by up to 4
functions
Note: Data cable (7522616) and contact temperature
Data cable 10 m long
To connect the boiler control unit and controller module
Note: The total length of all cables must not exceed 1000 ft.
Temperature sensor for heating circuit
Controller module in a plastic enclosure for wall mounting
Width 13 in. (325 mm), height 8 in. (195 mm),
depth 3 in. (75 mm)
sensors (7528121) required (not part of standard
delivery)
Prefabricated data cable CAN bus LiYCY 2 x 2 x 0.34 mm²
(300 m).
Contact temperature sensor Pt1000
Electrical