VII. Electrical
A.
General. Install wiring and ground boiler in accordance
with requirements of authority having jurisdiction, or in
absence of such requirements the National Electrical
Code, ANSI/NFPA 70, and/or the CSA C22.1 Electric
Code.
B.
Install thermostat. Locate on inside wall
approximately 4 feet above floor. Do not install on
outside wall, near fireplace, or where influenced by
drafts or restricted air flow, hot or cold water pipes,
lighting fixtures, television, or sunlight. Allow free air
movement by avoiding placement of furniture near
thermostat.
20
C
. Wire thermostat. Provide Class II circuit between
thermostat and boiler. Set thermostat heat anticipator to
0.6 amps. See Figure 20.
D.
Wire boiler. Boiler is rated for 120 VAC, 60 hertz, less
than 12 amperes. A separate electrical circuit must be
run from the main electrical service with an over-
current device/disconnect in the circuit. A service
switch is recommended and may be required by some
local jurisdictions. Connect circuit to black and white
wires and green ground screw. See Figure 20.
Figure 20: Wiring Diagram