IPM over(Over Current) error (Error Code : E464)
Is service valve fully opened?
Is compressor wire connected properly to the
compressor?
Check the compressor.
1. Are all the resistance values
between phases matched?
(U
V, U
2. Is compressor wiring normal? (disconnection, wrong
connection)
3. Is there any abnormal noise from
compressor rotation?
Is there a reading of MegaΩ of resistance between
compressor body and chassis?
Are the position and measuring value of the
temperature sensor normal?
Continue
Yes
W, V
W)
Yes
Yes
Yes
Continue
(cont.)
No
No
Check the connection status of compressor.
1. Replace the compressor : If the resistance value
between phases of the compressor is different.
No
End the service.
2. Reassemble wire : If the wire connection of the
compressor is wrong.
End the service.
3. Replace the compressor : When loud abnormal
noise generates (metal cutting or grinding noise),
or severe vibration.
No
No
Turn off the power and change the location of the
4-49
Open the valve.
Power on. Check the normal operation.
Power on.
Check the normal operation.
Replace the compressor.
temperature sensor or replace it.
Troubleshooting