Installation
Not recommended but in case of emergency
You must use a torque wrench but if you are obliged to install the unit without a torque wrench, you may
follow the installation method mentioned below.
After the work is finished, make sure to check that there is no gas leak.
When you keep on tightening the flare nut with a spanner, there is a point where the tightening torque suddenly
increases. From that position, further tighten the flare nut the angle shown below:
 After checking the pipe-connection for gas leakage, be sure to insulate the liquid and gas pipe, referring to Fig.9, 10
and the following points.
FXMQ48MFVJU
1. Insulate the liquid and gas pipes using the insulation for fitting (accessory 3), 4))
(Tighten both edges with clamping material.)
2. Make sure the insulation for fitting (accessory 4)) on the gas pipe has its seams facing up.
3. For the gas pipe, wrap the sealing pad (accessory 5)) around the insulation for fitting (accessory 4)) (flare nut part)
FXMQ72 · 96MFVJU
1. Insulate the liquid pipe using the insulation for fitting (accessory 3)).
(Tighten both edges with clamping material.)
2. Use the attached pipe (accessory 1)) for connecting the gas pipes and make sure to insulate the gas pipes (using
field supplied insulation) all the way to the base where they connect to the unit.
3. The turning torque of the hexagon head bolts (accessory 8)) to connect the attached pipe (accessory 1)) to the unit is
15.9 - 21.3ft/lbf.
Liquid
pipe
24
Further tightening
Pipe size
φ 3/8"
60 to 90 degrees
φ 5/8"
30 to 60 degrees
Insulation
(Attached with main body)
Eliminate a gap
Main body
Clamps (accessory 11))
Gas pipe
Liquid
pipe
Fig. 9
Eliminate
a gap
Insulation
(Attached with
main body)
Gas
pipe
Insulation
(Attached with
main body)
Clamps
(accessory 11))
Fig. 10
Table 3
Recommended arm length of
angle
tool
Approx. 7-7/8in.
Approx. 11-13/16in.
Insulation
Sealing pad
for fitting
(accessory 5))
(accessory 4))
Flare nut
Insulation (Field supply)
Insulation for fitting
Eliminate a gap
(accessory 3))
Main body
Insulation
(Attached with
main body)
Flare nut
Clamps
(accessory 11))
Insulation
(Field supply)
Attached pipe
(accessory 1))
Main body
Spring washer (accessory 7))
Hexagon head bolt (accessory 8))
Eliminate
Insulation for fitting
a gap
(accessory 3))
Main body
Insulation
(Field
supply)
Flare nut
Insulation
(Field supply)
EDUS39-900-F10
FXMQ-MF

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Fxmq48mfvjuFxmq72mfvjuFxmq96mfvju

Table of Contents