Installation
Wiring Example And How To Set The Remote Controller
HOW TO CONNECT WIRINGS (Remove the electric parts box lid and wire as shown in the
figure below.)
 Power supply wire, Ground wire (Refer to Fig. 17)
Connect the wire to L1 and L2 on the power supply terminal block (X1M). Also, connect the ground wire to the ground
terminal. Take the power supply wire and the ground wire into the unit through the wiring through hole <1>, and firmly
secure them together using the clamp (accessory 11)).
 Transmission wire, Remote controller wire (Refer to Fig. 17)
Connect the transmission wire to F1 and F2 on the transmission terminal block (X2M). Connect the remote controller
wire to P1 and P2 on the transmission terminal block (X2M). Take them into the unit through the wiring through hole
<2>, and firmly secure the wires using the clamp (accessory 11)).
CAUTION
 Wire the electrical components box so that the wiring is at least 3/8in. above the bottom of the electrical components
box.
 Be sure to attach the sealing material or putty (field supplied) to the wiring through holes to prevent the infiltration of
water as well as any insects and other small creatures from outside. Otherwise a short-circuit may occur inside the
electrical components box.
28
Transmission
terminal block (X2M)
Remote controller
wire
Transmission
wire
Electrical components
box lid
Clamp
(accessory 11))
Wire locking
bracket
Fig. 16
Electrical components box
A1P
X1M
X2M
Wiring
through
hole <2>
Insulation tube
(accessory 2))
Power supply
terminal block (X1M)
Lock nut
Conduit
(Field
(Field
supply)
supply)
Power supply
wire
Ground wire
Wiring
(Remote controller
and transmission)
X3M
Ground
terminal
Wiring
L
N
through
hole <1>
Clamp
(accessory 11))
Clasp
Fig. 17
EDUS39-900-F10
FXMQ-MF