Functional data (temperature with QSM2162)
Range of use
Measuring range
Measuring accuracy at DC 24 V in the range of
20...25 ° C
15...35 ° C
-35...50 ° C
Time constant t
Output signal, linear (terminal X3)
Functional data (humidity with QSM2162)
Range of use
Measuring range
Measuring accuracy at 23 ° C and DC 24 V
0...95 % r.h.
30...70 % r.h.
Time constant t
Output signal, linear (terminal X2)
Functional data
Max. air velocity V
Ambient conditions and protection classification
Protection degree of housing
Protection class
Environmental conditions
Transport
Climatic conditions
Mechanical conditions
Operation
Climatic conditions
Mechanical conditions
14
Siemens
Smart Infrastructure
63
63
max
– Temperature
– Humidity
– Temperature (housing with electronics)
– Humidity
-5...45 ° C
0...50 ° C/-35...35 ° C
± 0.3 k (typical)
± 0.6 k
± 1 k
< 3.5 min in 2 m/s moved air
DC 0...10 V or DC 0...5 V
0...50 ° C/-35...35 ° C, max. ± 1 mA
4...20 mA
0...50 ° C/-35...35 ° C, max. 500 ohm
5...95 % r.h. (non-condensing)
0...100 % r.h.
± 5 % r.h.
± 3 % r.h. (typical)
Approx. 20 s
DC 0...10 V or DC 0...5 V
0...100 % r.h., max. ± 1 mA
4...20 mA
0...100 % r.h., max. 500 ohm
10 m/sec
IP54 as per EN 60529 in built-in state
III as per EN 60730-1
IEC 60721-3-2
Class 2K3
-25...70 ° C
< 95 % r.h.
Class 2M2
IEC 60721-3-3
Class 3K5
-5...45 ° C
5...95 % r.h. (non-condensing)
Class 3M2