7.6.4.2 General considerations

7.6.4.3 Minimum values for insulation resistance

7.6.4.4 Stator winding insulation resistance measurement

3BFP 000 063 R0101 REV D
The following consideration should be noted, before deciding any actions based upon the
insulation resistance tests:
If the measured value is considered too low the winding must be cleaned and/or dried. If
these measures are not sufficient, expert help should be acquired
Machines, that are suspected to have moisture problem, should be dried carefully
independent of the measured insulation resistance value
The insulation resistance value will decrease when the winding temperature rises
The resistance is halved for every 10 ... 15 K temperature rise.
NOTE: The insulation resistance indicated in the test report is normally considerably higher
than the values measured on site.
Criteria for windings in a normal condition:
Generally, the insulation resistance values for dry windings should exceed the minimum values
significantly. Definite values are impossible to give, because resistance varies depending on the
machine type and local conditions. In addition, the insulation resistance is affected by the age
and usage of the machine. Therefore, the following values can only be considered as guidelines.
The insulation resistance limits, which are given below, are valid at 40 °C, and when the test
voltage has been applied for 1 minute or longer.
Rotor
For induction machines with wound rotors: R(
NOTE: Carbon dust on slip rings and naked copper surfaces lower the insulation resistance
values of the rotor.
Stator
For new stators: R(
1-10 min at 40 °C
and humid, R(
1-10 min at 40 °C
For used stators: R(
1-10 min at 40 °C
NOTE: If the values given here are not reached, the reason for the low insulation resistance
should be determined. A low insulation resistance value is often caused by excess
humidity or dirt, although the actual insulation is intact.
The insulation resistance is measured using an insulation resistance meter. The test voltage is
1000 VDC. The test time is 1 minute, after which the insulation resistance value is recorded.
Before the insulation resistance test is conducted, the following actions must be taken:
Check that the secondary connections of the current transformers (CT's), including spare
cores are not open. See Figure 7-3 Connections of the stator windings for insulation
resistance measurements
Verify that all power supply cables are disconnected
Manual for High Voltage Process Performance Motors
1-10 min at 40 °C
) > 1000 MΩ. If the measuring conditions are extremely warm
) values above 100 MΩ can be accepted
) > 100 MΩ
) > 5 MΩ
Maintenance - 63