■[F30] Accumulated flow value hold setting

Select the setting in which the accumulated flow measurement value is stored to the internal memory.
The default setting is not to store the accumulated flow when the power supply is turned off.
This function enables the accumulated flow value to be stored in permanent memory every 2 or 5 minutes.
The internal memory life varies depending on the number of times that the memory device can be accessed,
so this must be taken into account before use.
If the product is operated 24 hours per day, the maximum writable limit will be as follows:
Data memorized every 5 minutes --- 5 minutes x the number of times the memory device can be accessed
(3.7 million cycles) = 1850 million minutes = Approx. 35 years
Data memorized every 2 minutes --- 2 minutes x the number of times the memory device can be accessed
(3.7 million cycles) = 740 million minutes = Approx. 14 years
<Operation>
Press the UP or DOWN button in function selection mode to display [F30].
Accumulated flow value hold setting
Select the accumulated flow value hold setting by pressing the UP or
DOWN button.
Press the SET button to set.
: Data memorization is performed every 2 or 5 minutes (depending upon the setting chosen), this means that the accumulated flow
value for up to 2 or 5 minutes before the power supply is turned off will not be added to the device memory.
When the power supply is turned on again, the accumulated flow count will start from the value recorded at B.
Press the SET button.
[F30] Accumulated flow value hold setting is completed.
Move to the accumulated flow value hold setting.
Return to function selection mode.