■[F30] Accumulated flow value hold setting
The accumulated flow value can be held for 2 or 5 minutes.
<Operation>
Press the UP or DOWN button in function selection mode to display [F30].
Accumulated flow value hold setting
Press the UP or DOWN button to select the
accumulate flow value hold.
Press the SET button to set.
: When using the Accumulated flow hold function, calculate the product life according to the operating conditions, and use the product
within its life. The limit of the number times the memory can be written to is 3.7 million times. If the product is operated 24 hours per
day, the life will be as follows.
▪Data stored every 5 minutes: 5 minutes x 3.7 million cycles = 18.5 million minutes = 35 years
▪Data stored every 2 minutes: 2 minutes x 3.7 million cycles = 7.4 million minutes = 14 years
: The value is stored in memory every 2 or 5 minutes. If the power supply is turned off, the accumulated flow since the last time it was
stored will be lost.
: When the power supply is turned on again, the accumulated flow count will start from the last value recorded at B.
Press the SET button.
[F30] Setting of accumulated flow value hold completed
Move to the accumulated flow value hold setting.
Return to function selection mode.