Setpoint
Behavior
CalOverride
Overrides CT calibration.
When set to OFF, the inverter detects the CTs number and direction of
CTs.
A value of ON assumes a specific orientation and direction of CTs.
CTTurnsRatio
Turns ratio of the CTs installed.
Default turns ratio of 1,500 is compatible with included clamp type CTs
If installation restriction requires larger accessory CTs, set point shall be
adjusted to 3,000. Verify turn ratio of CTs before modifying this setting.
Event Name
Event Code
ct cal = 1
0x8061
ct cal = 2
0x8062
ct cal = 3
0x8063
ct cal = 4
0x8064
ct cal = 5
0x8065
ct cal = 6
0x8066
ct cal = 7
0x8067
ct cal = 9
0x8069
ct cal = A
0x806A
ct cal = B
0x806B
ct cal = C
0x806C
ct cal = D
0x806D
ct cal = E
0x806E
ct cal = F
0x806F
ct cal success
0x8070
Installation Manual for Generac PWRCell Inverter
Table 5-10. CT Setpoints
Table 5-11. Automatic Detection Troubleshooting Table
Description
Line 1 doesn't have a valid CT calibration
Line 2 doesn't have a valid CT calibration
Line 1 & 2 don't have a valid CT calibration
Line 3 doesn't have a valid CT calibration
Line 1 & 3 don't have a valid CT calibration
Line 2 & 3 don't have a valid CT calibration
Line 1 & 2 & 3 don't have a valid CT calibration
Line 1 has multiple CTs on it (or a CT is on the
neutral wire)
Line 2 has multiple CTs on it (or a CT is on the
neutral wire)
Lines 1 and 2 have multiple or missing CTs on
them (or a CT is on the neutral wire)
Line 3 has multiple CTs on it (or a CT is on the
neutral wire)
Lines 1 & 3 have multiple or missing CTs on them
(or a CT is on the neutral wire)
Lines 2 & 3 have multiple or missing CTs on them
(or a CT is on the neutral wire)
Lines 1 & 2 & 3 have multiple or missing CTs on
them (or a CT is on the neutral wire)
Calibration was successful
Electrical Connections
Default
Units
OFF
N/A
1,500
Turns
Possible Solution
Check wiring and CT integrity
Check wiring and CT integrity
Check wiring and CT integrity
Check wiring and CT integrity
Check wiring and CT integrity
Check wiring and CT integrity
Check wiring and CT integrity
Check wiring and CT integrity
Check wiring and CT integrity
Check wiring and CT integrity
Check wiring and CT integrity
Check wiring and CT integrity
Check wiring and CT integrity
Check wiring and CT integrity
Check wiring and CT integrity