Lennox ELITE Series Installation Instructions Manual page 30

Upflow / horizontal air discharge
Table of Contents

Advertisement

Details of Exhaust Piping Terminations for Non-Direct
Vent Applications
Exhaust pipes may be routed either horizontally through
an outside wall or vertically through the roof. In attic or
closet installations, vertical termination through the roof is
preferred. FIGURE 43 and FIGURE 45 show typical ter-
minations.
1 - Exhaust piping must terminate straight out or up as
shown. The termination pipe must be sized as listed
in table 8.The specified pipe size ensures proper
velocity required to move the exhaust gases away
from the building.
2 - On field supplied terminations for side wall exit,
exhaust piping may extend a maximum of 12 inches
(305MM) for 2" PVC and 20 inches (508MM) for 3"
(76MM) PVC beyond the outside wall
12" (305mm)
ABOVE AVE.
SNOW
ACCUMULATION
3" (76mm) OR
2" (51mm) PVC
PROVIDE SUPPORT
FOR EXHAUST LINES
NON-DIRECT VENT ROOF TERMINATION KIT
(15F75 or 44J41)
FIGURE 43
3 - If exhaust piping must be run up a side wall to position
above snow accumulation or other obstructions,
piping must be supported every 24 inches (610MM).
When exhaust piping must be run up an outside wall,
any reduction in exhaust pipe size must be done
after the final elbow.
4 - Distance between exhaust pipe terminations on
multiple furnaces must meet local codes.
Crawl Space and Extended Horizontal Venting
Lennox provides kit 51W18 (USA) and kit 15Z70 (Cana-
da) to install 2" or 3" PVC exhaust piping through the floor
joists and into the the crawl space. See FIGURE 44.
This kit can also be used as a supplemental drain for in-
stallations with condensate run back in the vent pipe (ie.
long horizontal runs, unconditioned spaces, etc.).
UNCONDITIONED
ATTIC SPACE
NOTE - Do
tical discharge through an existing unused chimney or stack is required, insert piping
inside
trated. In any exterior portion of chimney, the exhaust vent must be insulated.
Condensate Piping
This unit is designed for either right- or left-side exit of
condensate piping in upflow applications. In horizontal
applications, the condensate trap must extend below the
unit. An 8" service clearance is required for the conden-
sate trap. Refer to FIGURE 46 and FIGURE 48 for con-
densate trap locations. FIGURE 54 shows trap assembly
using 1/2" PVC or 3/4" PVC.
NOTE - If necessary the condensate trap may be installed
up to 5' away from the furnace. Use PVC pipe to connect
trap to furnace condensate outlet. Piping from furnace
must slope down a minimum of 1/4" per ft. toward trap.
Page 30
Venting In A Crawl Space
Basement Floor
FIGURE 44
NON-DIRECT VENT APPLICATION
USING EXISTING CHIMNEY
Minimum 12" (305MM)
above chimney top
plate or average snow
accumulation
SHEET
METAL TOP
PLATE
INSULATE
TO FORM
SEAL
FIGURE 45
KIT 51W18
(USA)
KIT 15Z70
(CANADA)
STRAIGHT-CUT OR
ANGLE-CUT IN DIRECTION
OF ROOF SLOPE
SHOULDER OF FITTINGS
PROVIDE SUPPORT
OF PIPE ON TOP PLATE
EXTERIOR
PORTION OF
CHIMNEY

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents