INSTALLATION
TUBING CONNECTIONS
Air Supply Pressure
CAUTION
Air Supply Filtering
TUBING CONNECTIONS
3 - 8
4. Lock all linkage components in place.
CAM
CAM FOLLOWER ARM
Figure 3-8. Cam Roller Alignment
Type AV positioners are available with (Type AV___1___ and
AV___2___) or without (AV___0___) manifolds. The following out-
lines supply air information and describes the piping connections.
Do not exceed the maximum supply pressure of 1034 kilo-
pascals (150 pounds per square inch gage). Exceeding this
pressure could cause equipment damage.
The air supply pressure range is 172 to1034 kilopascals (25 to
150 pounds per square inch gage).
NOTE: The minimum supply pressure should be 34.4 kilopas-
cals (5 pounds per square inch gage) above the operating pres-
sure required by the actuator.
An external filter is recommended for Type AV positioners for pri-
mary filtration of the supply air. ABB provides supply air filters as
accessories. Refer to Table
NOTE: Primary air supply filters are recommended for position-
ers with a manifold (AV___1/2___), without a manifold
(AV___0___) or with a gage block (AV___3___).
CAM ROLLER
1-12
for part numbers.