TZIDC DIGITAL POSITIONER | DS/TZIDC-EN REV. G
... Specification

Pneumatic connections

Cable
Thread ½-14 NPT
Thread M20 × 1.5
Thread M20 × 1.5
Thread G ½
(Optional: with cable gland(s) and blind plugs as necessary)
Compressed air output
Range
Standard design:
Marine version:
Air capacity
> 5 kg/h = 3.9 Nm3/h = 2.3 scfm at 1.4 bar
(20 psi) supply air pressure
> 13 kg/h = 10 Nm3/h = 6 scfm at 6 bar
(90 psi) supply air pressure
Output function
For single acting or double acting actuators
Air is vented from actuator / actuator is
blocked in case of (electric) power failure
Shut-off values
End position 0 % = 0 to 45 %
End position 100 % = 55 to 100 %
Instrument air*
Purity
Maximum particle size: 5 μm
Maximum particle density: 5 mg/m
Oil content
Maximum concentration 1 mg/m
Pressure dew point
10 K below operating temperature
Supply pressure**
Standard design:
1.4 to 6 bar (20 to 90 psi)
Marine version:
1.6 to 5.5 bar (23 to 80 psi)
Air consumption***
< 0.03 kg/h / 0.015 scfm
*
Free of oil, water and dust in accordance with DIN / ISO 8573-1,
pollution and oil content according to Class 3 (except for natural gas
variant)
** Do not exceed the maximum output pressure of the actuator
*** Independent of supply pressure
Thread ¼-18 NPT
Thread ¼-18 NPT
Thread G ¼
Thread Rc ¼
0 to 6 bar (0 to 90 psi)
0 to 5.5 bar (0 to 80 psi)
3
3
Accessories

Mounting material

Attachment kit for linear actuators in accordance with
Air Pipe
DIN / IEC 534 / NAMUR
Attachment kit for rotary actuators in accordance with
VDI / VDE 3845
Attachment kit for integral mounting
Attachment kit for actuator-specific mounting
Pressure gauge block
With pressure gauges for supply air and output pressure.
Pressure gauges with housing ø 28 mm (1.10 in), with
connection block in aluminum, black
Installation material in black for mounting on positioner

Filter regulator

All metal version in brass, varnished black, bronze filter
element (40 µm), with condensate drain.
Max. pre-pressure 16 bar (232 psi).
Output can be adjusted to:
1.4 to 6 bar (20 to 90 psi)
Marine version:
1.6 to 5.5 bar (23 to 80 psi)
The filter regulator may only be installed in combination with
the pressure gauge block (accessory).
PC adapter for communication
LCI adapter – USB for plug connection to positioner
HART® – USB modem for HART communication
Control program for operation and parameterization on
a PC
DAT200 Asset Vision Basic with DTM for TZIDC / TZIDC-200
on CD-ROM.
Download DTM for TZIDC at: www.abb.com/positioners.
Download ABB Ability™ Field Information Manager (FIM)
and FDI package at: solutions.abb/fieldinfo.