12
TZIDC DIGITAL POSITIONER | DS/TZIDC-EN REV. G
—
... Specification
Pneumatic connections
Cable
Thread ½-14 NPT
Thread M20 × 1.5
Thread M20 × 1.5
Thread G ½
(Optional: with cable gland(s) and blind plugs as necessary)
Compressed air output
Range
Standard design:
Marine version:
Air capacity
> 5 kg/h = 3.9 Nm3/h = 2.3 scfm at 1.4 bar
(20 psi) supply air pressure
> 13 kg/h = 10 Nm3/h = 6 scfm at 6 bar
(90 psi) supply air pressure
Output function
For single acting or double acting actuators
Air is vented from actuator / actuator is
blocked in case of (electric) power failure
Shut-off values
End position 0 % = 0 to 45 %
End position 100 % = 55 to 100 %
Instrument air*
Purity
Maximum particle size: 5 μm
Maximum particle density: 5 mg/m
Oil content
Maximum concentration 1 mg/m
Pressure dew point
10 K below operating temperature
Supply pressure**
Standard design:
1.4 to 6 bar (20 to 90 psi)
Marine version:
1.6 to 5.5 bar (23 to 80 psi)
Air consumption***
< 0.03 kg/h / 0.015 scfm
*
Free of oil, water and dust in accordance with DIN / ISO 8573-1,
pollution and oil content according to Class 3 (except for natural gas
variant)
** Do not exceed the maximum output pressure of the actuator
*** Independent of supply pressure
Thread ¼-18 NPT
Thread ¼-18 NPT
Thread G ¼
Thread Rc ¼
0 to 6 bar (0 to 90 psi)
0 to 5.5 bar (0 to 80 psi)
3
3
Accessories
Mounting material
•
Attachment kit for linear actuators in accordance with
Air Pipe
DIN / IEC 534 / NAMUR
•
Attachment kit for rotary actuators in accordance with
VDI / VDE 3845
•
Attachment kit for integral mounting
•
Attachment kit for actuator-specific mounting
Pressure gauge block
•
With pressure gauges for supply air and output pressure.
Pressure gauges with housing ø 28 mm (1.10 in), with
connection block in aluminum, black
•
Installation material in black for mounting on positioner
Filter regulator
All metal version in brass, varnished black, bronze filter
element (40 µm), with condensate drain.
Max. pre-pressure 16 bar (232 psi).
Output can be adjusted to:
•
1.4 to 6 bar (20 to 90 psi)
Marine version:
•
1.6 to 5.5 bar (23 to 80 psi)
The filter regulator may only be installed in combination with
the pressure gauge block (accessory).
PC adapter for communication
•
LCI adapter – USB for plug connection to positioner
•
HART® – USB modem for HART communication
Control program for operation and parameterization on
a PC
DAT200 Asset Vision Basic with DTM for TZIDC / TZIDC-200
on CD-ROM.
•
Download DTM for TZIDC at: www.abb.com/positioners.
•
Download ABB Ability™ Field Information Manager (FIM)
and FDI package at: solutions.abb/fieldinfo.