Appendix

A
Inspection and maintenance work
The table below lists the manufacturer requirements with respect to minimum inspection and maintenance intervals. If na-
tional regulations and directives require shorter inspection and maintenance intervals, you should observe these instead of
the intervals listed. Each time inspection and maintenance work is carried out, carry out the required preparatory and com-
pletion work.
#
Maintenance work
1
Record all of the analysis results in the Benchmark Checklist in these
instructions
2
Ask the end user whether any significant problems occur when operating
the product
3
Use the diagnostics system to check the product's fault history
4
Visually inspect whether the air/flue pipe and its opening have been in-
stalled correctly in accordance with the set-up instructions
5
Check that the unit has been installed correctly and the connections have
been secured
6
Check that the condensate pipe is in good condition, that it is leak-tight
and that the drain is correct
7
Check whether all of the externally routed condensate pipes are dimen-
sioned correctly and have been insulated sufficiently (frost protection)
8
Check whether the gas flow rate corresponds with the specifications on
the data plate and lies within the tolerances specified in these instructions
9
If the gas flow rate lies outside of the tolerances specified in these in-
structions, eliminate the fault in accordance with the regulations and the
current technology
10
Check the general condition of the product and, if required, eliminate any
faults that are found
11
Checking and, if required, adjusting the CO₂ content and the CO/CO₂
ratio (air ratio setting)
12
Logging the CO
13
Disconnect the product from the electrical installation
14
Check that the connections/electrical plug connections have been con-
nected correctly/function correctly (product must be voltage-free)
15
Check the product's recirculation at the supply air test point on the air/flue
pipe. If required, inspect the entire air/flue system and, if necessary, cor-
rect the fault
16
Removing dirt from the product and the vacuum chamber
17
Visually check the heat cell to ascertain its condition and detect any cor-
rosion, rust or damage, and carry out maintenance work, if required
18
Check that the gas stopcock and service valves function correctly
19
Check the quality of the heating water: Clarity (clouding), correct inhibitor
and pH value
20
Removing the compact thermal module
21
Check the burner for damage
22
Checking the insulating mats in the combustion area and replacing dam-
aged insulating mats
23
Cleaning the heat exchanger
24
Checking the condensate trap for dirt and cleaning it
25
Installing the compact thermal module
26
Cleaning the strainer in the cold water inlet
27
Check the impeller sensor for dirt/damage
28
If the water volume is insufficient (domestic hot water) or the outlet tem-
perature is insufficient, check the secondary heat exchanger
29
Checking the pre-charge pressure of the expansion vessel
30
Checking the pre-charge pressure in the shift-load cylinder expansion
vessel
31
Reassemble the product
48
content (air ratio) and CO/CO
2
Interval
Annually
Annually
Annually
Annually
Annually
Annually
Annually
Annually
Annually
Annually
Annually
ratio
Annually
2
Annually
Annually
Annually
Annually
Annually
Annually
Annually
at regular intervals
at regular intervals
at regular intervals
at regular intervals
at regular intervals
at regular intervals
at regular intervals
at regular intervals
at regular intervals
at regular intervals
Annually
After each time maintenance
work is carried out
Installation and maintenance instructions ecoTEC plus 0020244998_04
33
37
38
39
39