Engineering; Hardware Setup - Siemens SIMATIC RTU3041C Manual

Monitoring of remote measurement points
Hide thumbs Also See for SIMATIC RTU3041C:
Table of Contents

Advertisement

2 Engineering

Engineering
2
2.1

Hardware Setup

Section 1.3
The following diagram shows the hardware setup of the RTU3041C.
Figure 2-1: Circuit diagram RTU
External power
supply (optional)
1. Insert the SIM card into the RTU3041C.
2. Insert two batteries at a time into a battery module housing.
3. Mount the RTU3041C and, to the left of it, the battery module housing on a
top-hat rail.
4. Connect the digital level sensor to the terminal block X20.
5. Connect the digital moisture sensor to terminal block X21.
6. Connect the analog level sensor to terminal blocks X40 and X41. For
instructions on how to operate the SITRANS LU150, refer to the instruction
manual: https://support.industry.siemens.com/cs/ww/en/view/109739505.
7. Connect the antennas to the RTU3041C.
8. Connect the battery module housing to the RTU3041C.
Monitoring of Remote Measurement Points
Entry ID: 109739240,
V3.0,
lists the required hardware components.
Digital
level sensor
M
X20
X10
L+
06/2021
Digital
moisture sensor
M
1
0
X21
RTU3041C
X41
X40
L+
M
M
0+ 0-
+
-
LU150
... ...
8