A description of each fault and suggested remedies are as
follows:
No LED - Discharged Battery
If there is a detected fault condition but the LED is not
blinking, this is because the battery is completely discharged.
To remedy the problem, remove the 15 Amp fuse and
disconnect the battery from the generator. Take the battery
to a local battery store for analysis. Replace the battery after
it has been fully recharged, connecting the NEGATIVE cable
last. Then install the 15 Amp fuse in the control panel.
NOTE: With the battery installed, all wiring to transfer switch
and home generator completed, utility power supplied to
the Automatic Transfer Switch, and the unit in AUTO mode,
the battery receives a trickle charge while the engine is not
running. The trickle charge is not able to recharge a battery
that is completely discharged. See Battery in Maintenance.
Low Battery Voltage
This fault is indicated by fault code FC_1 and one blink on the
LED indicator. This condition occurs if the generator cannot
start because the starting battery output power is below that
needed to crank the engine. Causes for this problem may be
a faulty battery or battery charge circuit.
To remedy the problem, contact your local service center to
check the battery charge output. Remove the 15 Amp fuse
and disconnect the battery from the generator. Take the
battery to a local battery store for analysis.
Replace the battery after it has been fully recharged,
connecting the NEGATIVE cable last. Then install the 15 Amp
fuse.
Low Oil Pressure
This fault is indicated by fault code FC_2 and two blinks on
the remote LED indicator. The unit is equipped with an oil
pressure switch (A). The oil drain connection (B) is shown
for identification.
A
B
The oil pressure switch uses normally closed contacts that
are held open by engine oil pressure during operation.
Should oil pressure drop below the 8 psi range, switch
contacts close and the engine is shut down.
To remedy the low oil pressure condition, add the
recommended oil to the FULL mark on the dipstick.
If the low oil pressure condition still exists, the engine will
start, then shut down after about 20 seconds. The fault code
will appear and the LED will flash. In this case, contact a
Briggs & Stratton Authorized Dealer.
Low Voltage (Generator)
This fault is indicated by fault code FC_3 and three blinks on
the LED indicator. This condition is caused by a restriction in
the fuel flow, a broken or disconnected signal lead, a failed
alternator winding, the control panel circuit breaker is open,
or the generator is overloaded.
To remedy the problem, contact your installer or a Briggs &
Stratton Authorized Dealer.
Engine Fail To Start
This fault is indicated by fault code FC_4 and four blinks on
the LED indicator. This feature prevents the generator from
damaging itself if it continually attempts to start in spite
of another problem, such as no fuel supply. Each time the
system is directed to start, the unit will crank for 10 seconds,
pause for 10 seconds, and repeat. If the system does not
begin producing electricity after approximately 2 minutes, the
unit will stop cranking and the LED will blink.
Check to make sure the generator's main circuit breaker is in
the ON position in order for the sensing leads to verify that
the unit is running.
The most likely cause of this problem is no fuel supply.
Check the inside and outside fuel shut off valves to ensure
they are fully open. Other causes could be failed spark
plug(s), failed engine ignition, or the engine air filter
is clogged. You may need to contact your installer for
assistance if you can't remedy these problems.
Low Frequency
This fault is indicated by fault code FC_5 and five blinks on
the LED indicator. This feature protects devices connected
to the transfer switch by shutting the generator down
if the engine runs slower than 55 Hz for three seconds.
This condition is caused by a failed engine governor or by
excessive loads on the generator. To remedy the problem,
contact your installer or a Briggs & Stratton Authorized
Dealer.