Spare Parts; Technical Data - Apollo 55000-268 Installation Manual

Intelligent reflective beam detector
Hide thumbs Also See for 55000-268:
Table of Contents

Advertisement

Spare parts

If required, the following detector and refl ector parts can be ordered separately.
Detector head assembly
Refl ector (prism) for the 50m detector
Refl ector (prism) for the 100m detector (= 4x 50m refl ector)
Test fi lter

Technical Data

Part no 55000-268
Part no 55000-273
Supply Voltage
Supply Current
Prism targeting mode
Alignment mode
Run mode (quiescent)
Alarm (LED illuminated)
Fault (LED illuminated)
Power down reset time
Tolerance to beam misalignment
Alarm thresholds
25%
35%
50%
Optical Wavelength
Operating temperature
Dimensions
Width
Height
Depth
Weight
(at 35% obscuration)
5 to 50 metres (detector to refl ector)
50 to 100 metres (detector to refl ector)
17–28V DC (plus protocol)
17mA
17mA
5mA
9mA
5mA
>5 seconds
Detector ± 0.8° , prism ± 5.0°
2.50dB
3.74dB
6.02dB
880nm (infra red)
–20°C to 55°C
130mm
210mm
120mm
670 gm