Troubleshooting; Fault Fi Nding - Apollo 55000-268 Installation Manual

Intelligent reflective beam detector
Hide thumbs Also See for 55000-268:
Table of Contents

Advertisement

TROUBLESHOOTING

Before investigating individual beam detectors
for faults, it is very important to check that the
system wiring is fault free. Many fault conditions
are the result of simple wiring errors. Earth faults
on a data loop or any ancillary zone wiring may
cause communication errors.
Please also refer to Table 4 on page 17 for infor-
mation on diagnostics that may be supplied by
the beam detector.
Fault fi nding
Fault
Device not recognised
Unable to obtain amber fl ashing
alignment LED
Unable to obtain red fl ashing align-
ment LED
Amber fl ashing LED in operating
mode
Alarm condition without fi re
Red LED illuminates after alignment
Table 6
Possible Cause
Type code incompatibility
No power to detector
No power to detector
Beam out of alignment
Beam partially obscured
Transmitter/receiver contaminated
Environmental conditions
Panel software
20
Action
Contact control panel
manufacturer to check
compatibility
Check wiring
Check wiring
Align beam
Check beam line of sight
Clean lenses and/or refl ectors
Check for symptoms such as
condensation
Check analogue value at
control panel, then reset