Commissioning; Analogue Values - Apollo 55000-268 Installation Manual

Intelligent reflective beam detector
Hide thumbs Also See for 55000-268:
Table of Contents

Advertisement

COMMISSIONING

Analogue values

The beam detector returns a pre-set analogue
value corresponding to its status. These values
are defi ned in Table 4 below.
Analogue value
Table 4
The beam detector may return a pre-alarm
value before a full alarm condition occurs. The
analogue value depends on the smoke density
and the set obscuration level (described on page
7) as shown in Table 5.
Analogue value returned
Table 5
0
Microprocessor fault
1
Sensor fault
2
Prism (refl ector) targeting mode
3
Alignment mode
4
General fault warning
5
'Signal High' fault
6
Contamination compensation limit reached
20
Alignment drift negative
25
Detector normal
30
Alignment drift positive
32
Contamination compensation level low (40%)
33
Contamination compensation level medium (60%)
34
Contamination compensation level high (80%)
45–54
Pre–Alarm values (see Table 5 below)
64
Alarm
45
46
47
48
49
50
51
52
53
54
Percentage of obscuration indicated by pre-alarm
Signifi cance
Actual obscuration at set
obscuration level of
25%
35%
16
23
16
26
17
27
18
28
19
29
20
30
21
31
22
32
23
33
24
34
17
50%
33
34
35
36
38
40
42
44
46
48

Hide quick links: