PACD011001C2
1.6
Low Noise Operation
By connecting the external contact input to the low noise input of the BMS interface adaptor for outdoor unit
(optional), you can save power and lower operating noise by 2 -3 dB.
Instructions for
1. Outdoor unit field setting
‹ Setting mode 1: Set low noise operation to "ON."
Demand Control
‹ Setting mode 2: Match low noise operation and demand control address with address of BMS interface
Operation
2. BMS interface adaptor for outdoor unit setting
‹ Function switch (SS1)
Set to "BOTH" or "DE."
‹ Address setting switches (DS1, DS2)
Match with outdoor unit low noise operation and demand control address.
3. Short-circuit the low noise input of BMS interface adaptor for outdoor unit.
Low Noise Control
System Example
Test Operation UM Combination "MA1R Series" Using R-407C
adaptor for outdoor unit.
Test Operation