PROTECTIVE DEVICES

Protection devices and emergency stop devices are
designed as standard components for protection of the
generator against trouble during operation. The LCD on
the Digital Controller will inform the user when a fault has
occurred.
When a major fault is detected, such as low oil pressure,
high water temperature, and overspeed, the engine
automatically shuts down. Check the display for the fault
and correct the problem.
For minor faults, the engine will continue working. Stop the
engine and remedy the cause of the problem. The Digital
Controller will display the cause of the fault.
Before inspecting or troubleshooting the generator, press
the OFF button on the Digital Controller. Place the main
circuit breaker in the OFF position and allow sufficient time
for adequate cooling.
PAGE 38 — SG1400/1600C4F STUDIO GENERATOR • OPERATION MANUAL — REV. #0 (07/22/20)
PROTECTIVE DEVICES
After automatic shutdown, always inspect the generator
and eliminate any problems that might have caused the
shutdown before attempting to restart the generator.
When ready to restart, check and make sure that no
alarms are shown in the Alarm List on the Digital Controller.
Restart the generator as outlined in the Startup section of
this manual.
Refer to the InteliVision 5™ Controller User's Guide for
detailed information of faults and display information.
CAUTION
To prevent damage to the equipment and severe bodily
harm, even death, please follow all lock-out safety
procedures when performing maintenance.