Adjusting Temporary Override time length (continued)
4. Down button through entries to highlight Occ Override (Hrs)
5. Enter button to select Occ Override (Hrs)
6. Up/Down button(s) to adjust time
(1/2 hour increments, Max. 12 hours)
7. Enter button to select new override time limit
8. Left button to navigate back to Main Menu
9. Left button to navigate back to Home Screen
Indoor Blower Settings: The indoor blower can be set to always run at 100% capacity regardless of call,
and also to run in either continuous or auto mode during occupied (always) periods.
To access/change Blower Settings from the Home Screen, press:
1. Left button to highlight Current Operation Status Line
2. Down button to highlight Fan Status Line
3. Enter button to select Fan Status Line and enter
Fan Modes Screen
4. Down button through selections, adjust as necessary.
- Always 100%: "YES" = system blower always runs 100% speed regardless of compressor
modulation or stages of heating, "NO" = system blower modulates to specific speeds engineered
by factory for best efficiency (Factory Default)
- Unocc: Since scheduling is not active on this controller, this setting has no effect on fan operation.
- Occ: "ON" = system fan will run continuously during all operational modes (Factory
Default), "Auto" = system fan will operate during call for cooling or heating, but will cycle off
when no compressor or no heating is needed.
5. Enter button to save changes to Fan Modes Selections
- Repeat steps 4 through 5 for all changes to Fan Modes Selections
6. Left button to return to Home Screen
Setting Date/Time: Unless scheduling is desired, the absolute date and time are not necessary, and only
used for alarm reporting reference points. Not entering a date/time will have no operational effect upon
the controller.
To enter the current date and time from the Home Screen, press:
1. Right button to access Main Menu Screen
2. Down button through entries to highlight Date/Time
3. Enter button to select Date/Time and enter Date/Time Screen
4. Enter button to select Date:
5. Up/Down button(s) to adjust existing Month, Day, Year
6. Enter button to select new entry
7. Down button to highlight Time:
8. Up/Down button(s) to adjust existing Hours, Minutes, Seconds
9. Enter button to select new entry
10. Left button to navigate back to Main Menu
11. Left button to navigate back to Home Screen
Scheduling: Scheduling is not a necessary part of the initial programming. It is an optional function
meant to allow for setback temperatures during unoccupied periods. From the factory, the controller has
no scheduling and will only allow occupied setpoints unless otherwise scheduled. If scheduling is
desired, current Date/Time will be necessary (see above).