TROUBLESHOOTING
FAN BLADE SETTING DIMENSIONS
Shown in Figure 9 is the correct fan blade setting for
proper air delivery across the outdoor coil. Refer to
Table 1 for unit specific dimension.
Any service work requiring removal or adjustment in the
fan and/or motor area will require that the dimensions
below be checked and blade adjusted in or out on the
motor shaft accordingly.
FIGURE 9
FAN BLADE SETTING
TABLE 1
FAN BLADE DIMENSIONS
Model
Dimension A
W3RV2
1.25"
W3LV2
W5RV2
1.75"
W5LV2
W6RV1
1.75"
W6LV2
Manual 2100-615A
Page
20 of 24
REMOVAL OF FAN SHROUD
1. Disconnect all power to the unit.
2. Remove the screws holding both grilles, one on
each side of unit, and remove grilles.
3. Unwire condenser fan motor.
4. Remove the bolts and nuts holding the condenser
fan motor bracket to the fan shroud.
5. Slide the condenser fan motor and bracket to the
rear of the condenser section.
6. Remove screws holding fan shroud to condenser
and bottom support plate.
7. Slide fan shroud out the left side of the unit.
8. Reverse steps to install.
R-410A REFRIGERANT CHARGE
This unit was charged at the factory with the quantity
of refrigerant listed on the serial plate. AHRI capacity
and efficiency ratings were determined by testing with
this refrigerant charge quantity.
The following pressure tables show nominal
pressures for the units. Since many installation
specific situations can affect the pressure readings,
MIS-1724
this information should only be used by certified
technicians as a guide for evaluating proper system
performance. They shall not be used to adjust charge.
If charge is in doubt, reclaim, evacuate and recharge
the unit to the serial plate charge.