Greenheck ECV Series Installation, Operation And Maintenance Manual page 20

Energy core ventilator
Table of Contents

Advertisement

ordered). Filters should be checked and cleaned on
a regular basis for best efficiency. The frequency of
cleaning depends upon the cleanliness of the incoming
air. These filters should be cleaned prior to start-up.
Clean filters by rinsing with a mild detergent in warm
water.
Internal Filter Maintenance
The units will typically be provided with 2-inch, pleated
filters in the outdoor air and exhaust airstreams. These
filters should be checked per a routine maintenance
schedule and replaced as necessary to ensure proper
airflow through the unit. See table for pleated filter size
and quantity for each unit. Replacement filters shall be
of same performance and quality as factory installed
filters. Filter type must be pleated design with integral
metal grid. Two acceptable filter replacements are
Aerostar Series 400 or Farr 30/30
Outdoor Air Filters: Access to the outdoor air filters is
through the door labeled as "Filter Access" on the sides
Pleated Filter Size and Quantities
Supply
Unit Size
Size
ECV-10
20 x 25
ECV-20
20 x 20
ECV-30
20 x 20
ECV-40
20 x 20
All dimensions in inches.
of the unit.
Exhaust Air Filters: Access to the exhaust air filters is
through the door labeled as "Filter Access" on the sides
of the unit.
Refer to Access Panel Location section for additional
information on filter locations.
Door Seal Maintenance
A bulb seal is installed on the perimeter of the door
frame. Inspect at least annually to ensure that the seal is
still intact.
WARNING
Do not wash, soak in water, or use detergents and/
or cleaners on the fiber membrane core. This will
result in a damaged core and will not be covered by
the warranty.
WARNING
Energy core shall not be subjected to temperatures
greater than 140ºF. This will result in a damaged core
and will not be covered by warranty
Energy Recovery Core
The energy recovery core should be inspected and
cleaned based on the application requirements and core
type as outlined below.
20
Energy Core Ventilator
®
.
Exhaust
Qty
Size
Qty
1
20 x 25
2
2
20 x 20
2
3
20 x 20
3
4
20 x 20
4
Fiber Membrane
Frequency of cleaning - A regular cleaning cycle
must be established for the energy recovery core in
order to maintain optimum sensible and latent energy
transfer. In reasonably clean environments such as
schools, offices or retail stores, the energy recovery core
should be inspected annually and cleaned as needed.
Failure to follow a regular cleaning cycle for the energy
recovery core can result in significant energy transfer
performance losses.
Accessing the energy recovery core - Disconnect
the power to the unit. Remove access panel.
Removing the energy recovery core - Once the
energy core access doors are removed, the core can be
pulled from the housing. To replace the core, reverse the
procedure.
Recommended cleaning
procedure - Once the core is
removed, gently vacuum the
surfaces of the core to remove
the dirt and debris that has
accumulated.
Polymer Membrane
Frequency of cleaning - A regular cleaning cycle
must be established for the energy recovery core in
order to maintain optimum sensible and latent energy
transfer. In reasonably clean environments such as
schools, offices or retail stores, the energy recovery core
should be inspected annually and cleaned as needed.
Failure to follow a regular cleaning cycle for the energy
recovery core can result in significant energy transfer
performance losses.
Accessing the energy recovery core - Disconnect
the power to the unit. Remove access panel.
Removing the energy recovery core - Once the
energy core access doors are removed, the core can
be pulled from the housing. To replace the core, reverse
the procedure.
Recommended cleaning
procedure - Once the core is
removed, ensure that the plates
are orientated in a way for proper
draining. Use low pressure tap
water to clean the core. If the
core is extremely dirty, use a mild
detergent such as Dawn
®
solution no less than 1:100 parts water to soap.
WARNING
Do not use a high pressure water source (pressure
washer) or harsh, corrosive detergents. This will
result in a damaged core and will not be covered by
the warranty.
WARNING
Energy core shall not be subjected to temperatures
greater than 140ºF. This will result in a damaged core
and will not be covered by warranty
in a
®