Main menu boilers (1...6)

(Only with RMK770)
Menu Flue gas measuring mode
Refer to page Fehler! Textmarke nicht definiert..
Menu Boiler operating mode
• Preselection:
On = boiler released
Off = boiler locked; frost protection is ensured
• State:
On = boiler released
Off = boiler locked
• Cause:
Here, the reason for the boiler's state is given.
Siemens Building Technologies Technologies / HVAC Products
Menu Inputs / setpoints
Displayed are the values acquired by the inputs and the
associated setpoints and limit values. In addition, the
hours run counter and the burner start counter can be
read.
Menu Outputs
Displayed are for each output the state and thus the
operating state (on / off, open / closed) of the controlled
plant component. If a plant component is not present,
there will be no menu item either.
Menu Limitations
The current state of the limitations (Active/Inactive) is
displayed (useful information for the heating engineer).
Path: Main menu > Boiler ...