Analog Output Modules - Mitsubishi Electric MELSEC ST Series Installation Manual

Modular input/output system
Table of Contents

Advertisement

Specifications
2.2.7

Analog Output Modules

Item
Number of input channels
Analog output
Resolution
Conversion time
Maximum output
Total error
Resistance of the connected load
Isolation method
Dielectric withstand voltage
Insulation resistance
Noise durability
Indication of operating status
Number of occupied slices (Width)
Number of occupied
I/O points
Internal power consumption
(5 V DC)
Weight
18
ST1DA2-V
-10 to +10 V
0 to 10 V
0 to 5 V
1 to 5 V
±0.2 % (ambient temperature: 20 °C to 30 °C),
±0.4 % (ambient temperature: 0 °C to 20 °C and 30 °C to 55 °C)
> 1 k
(-10 to +10 V and 0 to 10 V)
> 500
(0 to +5 V and 1 to 5 V)
The output channels are isolated against the backplane bus by
photocouplers. There is no isolation between the channels.
500 V AC for 1 minute across the external DC terminals and FG
≥ 10 MΩ ( (across external DC terminals and FG,
Tested with noise simulator (Peak-to-peak noise voltage: 500 V,
noise width/noise frequency: 1 µs/25 to 60 Hz)
First transient noise compliant to IEC61000-4-4: 2 kV
Inputs
Outputs
2
12 bit + sign
max. 0.1 ms per channel
±12 V
checked with insulation resistance tester)
With LEDs RUN and ERR
1 slot (12.6 mm)
2
2
95 mA
0.03 kg
ST1DA1-I
1
0 to 20 mA
4 to 20 mA
±21 mA
< 500
95 mA
MITSUBISHI ELECTRIC