5 - ALARMS AND DIAGNOSTICS
A040 Gener. 3 Burner 3
A041 Gener. 3 Burner 4
A042 Gener. 4 Burner 1
A043 Gener. 4 Burner 2
A044 Gener. 4 Burner 3
A045 Gener. 4 Burner 4
A046 Gen. 1 Modbus Commun. : Faulty
A047 Gen. 2 Modbus Commun. : Faulty
A048 Gen. 3 Modbus Commun. : Faulty
A049 Gen. 4 Modbus Commun. : Faulty

5.1.1 - BSP and BUS lights on Tutorbit

Tutorbit has two lights, BSP and BUS (see Figure 3-1), the
state of which indicates device operation. The diagnostics can
be checked in the table below.
BSP light
Red and yellow alternating
every second
Green
Yellow
Flashing yellow
Flashing red
Steady red on

5.1.2 - Expansion BSP and BUS lights

The expansion has two lights, BSP and BUS (see Figure 3-2
and 3-3), the state of which indicates device operation. The
diagnostics can be checked in the table below.
BSP light
Flashing red
Green
COSMOGAS
Module 3 error alarm;
Module 3 error alarm;
Module 4 error alarm;
Module 4 error alarm;
Module 4 error alarm;
Module 4 error alarm;
Module 1 communication error
Module 1 communication error
Module 1 communication error
Module 1 communication error
Meaning
Software update
In operation
Programme loaded but not working
Programme not loaded
Software error
Hardware error
Meaning
Software error
In operation
Check the type of error on the generator
3 display;
Check the type of error on the generator
3 display;
Check the type of error on the generator
4 display;
Check the type of error on the generator
4 display;
Check the type of error on the generator
4 display;
Check the type of error on the generator
4 display;
Check the connection with the generator; Restore the connection;
Check the connection with the generator; Restore the connection;
Check the connection with the generator; Restore the connection;
Check the connection with the generator; Restore the connection;
BUS light
Off
Yellow
Green
Red
Flashing red
BUS light
Red
Green
Yellow
65
Restore by following the
instructions provided with
the generator;
Restore by following the
instructions provided with
the generator;
Restore by following the
instructions provided with
the generator;
Restore by following the
instructions provided with
the generator;
Restore by following the
instructions provided with
the generator;
Restore by following the
instructions provided with
the generator;
Meaning
Modem not connected
Modem connected and initialised but
communication is missing
Modem connected and communication
active
Modem connected but there is a
communication error (for example, the
provider has disappeared)
Software or hardware error
Meaning
Communication error
Correct communication
Communication correct but parameters not
fully configured
TUTORBIT