GP-IB interface functions
The following table lists GP-IB interface functions used in master mode or in slave mode.
Function
SH (source handshake)
AH (acceptor handshake)
C (controller)
T (talker)
L (listener)
SR (service request)
RL (remote, local)
PP (parallel poll)
DC (device clear)
DT (device trigger)
Master mode
SH1
Available (transmission function)
AH1
Available (reception function)
C1
• System controller
C2
• IFC transmission
C3
• REN transmission
C4
• Responding to the SRQ
C25
• Interface message transmission
• Parallel poll
• No delegation of authority of the controller
T8
Available
(the talker cancellation function by MLA
command available, the talking only mode
setting not available, the serial poll not
available)
L4
Available
(the listener cancellation function by MTA
command available, the listening only mode
setting not available)
SR0
Not available
(the serial poll can be performed)
RL0
Not available
PP0
Not available
(the parallel poll can be performed)
DC0
Not available
DT0
Not available
Slave mode
SH1
Available (transmission function)
AH1
Available (reception function)
C0
Not available
T6
Available
(the talker cancellation function by MLA command
available, the talking only mode setting not available,
the serial poll available)
L4
Available
(the listener cancellation function by MTA command
available, the listening only mode setting not
available)
SR1
Available
RL1
Available
PP1
The response function to the parallel poll available
DC1
Available
DT1
Available