51 | © 2019 ABB | 1SDH001316R1002 - ECN000086501 - Rev. A
Continued from the previous page
Signal
Suggestions
Ekip Sign 3T
Alarm for connection of one or more analog inputs to Ekip Signalling 3T module
connection
Ekip Sign 3T
One or more thresholds of the Ekip Signalling 3T module has/have been exceeded
threshold
Internal error
Internal error; contact ABB if this typoe of error occurs
Fault with Ekip Com modules: synchronization problem of SNTP synchronization
SNTP error
reference module
Measuring Error
Measurement module parameter reading error, contact ABB
Ethernet
No external cable on one or more Ekip Com modules with Ethernet connection
disconnected
IEEE1588 synch
Synchronization problem of IEEE 1588 synchronization reference module
MAC Address
Ekip Com module detected with incorrect / not allowed MAC address, contact ABB.
Ekip Installation
Installation error between HMI and Mainboard, contact ABB
Measuring
Install Measurement module (Settings-Circuit breaker-Installation-Measuring-Install)
installation
menu
Install Rating Plug (Settings-Circuit breaker-Rating Plug-Install menu) and check
RatingPlugInstallation
connection if there are further faults
Maintenance alarm: perform maintenance and then reset the alarm via Ekip Connect
Maintenance
(see 1SDH001330R1001)
PC Power exceed The average power limit setting of the Power Controller has been exceeded
Rating plug
Rating plug not present, value or size incompatible with Ekip Touch parameters
Zone Selectivity
Error in zone selectivity connections (Hardware Selectivity)
Diag
Fault in connection of sensors to Trip unit; check status of sensors, including external
Neutral, or call ABB
Sensor L1/L2/
L3/Ne
Check current sensors, status of terminal and cables connecting to Ekip Touch
Configuration
TFTP server enabled and/or configuration session open on module Ekip Com
Session
IEC61850 or Ekip Hub
The software versions between Mainboard and display (Ekip Touch) are not
compatible with each other: To restore compatibility, please consult ABB.
Software Not
NOTE: modification of all parameters is inhibited via display; if present,
Compatible
protections L, I and Iinst are active and function with the parameters prior to the
alarm (parameters of previous unit are active if display has been replaced)
CB status
CB state incorrect (esample: current present but CB in open state)
Disconnection of Trip coil detected, check functionality
TC disconnected
Check Trip coil, status of the terminal and cables connecting to Ekip Touch
Contact Wear
Make sure that the contacts/poles are in good condition.
Management operations | 1 - Ekip Touch maintenance and troubleshooting
ABB | SACE Emax 2
Continued on the next page