Table of Contents

Advertisement

4 - Operating features

Introduction Ekip Touch has been developed and certified to function in specific environmental, electrical and mechanical
Electrical characteristics The Ekip Touch measurement and protection functions described in this document are provided with primary
Self-supply The internal current sensors are able to supply the Trip unit directly; versions Hi-, G, G Hi- are also fitted
Auxiliary power supply Ekip Touch can be connected to an external auxiliary supply source, which is useful when certain functions
11 | © 2019 ABB | 1SDH001316R1002 - ECN000086501 - Rev. A
conditions; full details are available in the Technical catalog.
The following sections describe the electrical and power supply characteristics that enable Ekip Touch and
the relative electronic accessories to operate correctly.
voltage and current values within the following nominal ranges:
Parameter
Primary current
Primary voltage
Rated frequency
Peak factor
(1)
range with reference to each phase; In refers to the rated size defined by the Rating plug installed on the Trip
unit, available in models from 100 A to 6300 A
(2)
rated highest line-to-line voltage connected directly to Trip unit, also to sockets inside the CB; external
transformers must be used for higher voltage values, consult the chapter dedicated to the Measurement
modules
with the Measurement enabler with voltage sockets module, which allows the Trip unit to be supplied by the
installation voltages as well:
Parameter
Minimum three-phase turn-on current
Minimum three-phase turn-on voltage
such as communication via Local Bus, recording manual operations, certain measurements and the
datalogger must be activated.
The auxiliary supply can be provided by modules from the Ekip Supply range or by direct connection to the
terminal box.
Direct connection must guarantee the following operating conditions:
Parameter
Voltage
Tolerance
Maximum ripple
Maximum inrush current @ 24 V
Maximum rated power @ 24 V
Connection cable
IMPORTANT: if connection is direct, the power supply must be galvanically insulated
and provide the insulation characteristics established by standard IEC 60950 (UL
1950) or equivalent.
Rated operating range
0,004 ÷ 16 In
(1)
5 ÷ 690 V AC
(2)
45 ... 55 Hz (with fn= 50 Hz) / 54 ... 66 Hz (with fn= 60 Hz)
Complying with standard IEC 60947-2
Operating limits
> 30 A (E1.2-E2-2-E4.2 with Rating Plug < 400 A)
> 80 A (E1.2-E2-2-E4.2 with Rating Plug ≥ 400 A)
> 160 A (E6.2)
> 80 V
Operating limits
24 V DC galvanically isolated
±10%
±5%
10 A per 5 ms
4 W
Insulated with grounding cable (same characteristics as Belden
3105A/B or higher)