Parameter Descriptions
AN-44 Term. X30/12 Low Ref./Feedb. Value
Range:
Function:
0
[-999999.999 -
Sets the analog output scaling value to
*
999999.999]
correspond to the low voltage value set
in parameter AN-40 Terminal X30/12 Low
Voltage.
AN-45 Term. X30/12 High Ref./Feedb. Value
Range:
Function:
100
[-999999.999 -
Sets the analog input scaling value to
*
999999.999]
correspond to the high-voltage value
set in parameter AN-41 Terminal X30/12
High Voltage.
AN-46 Term. X30/12 Filter Time Constant
Range:
Function:
NOTICE
0.001 s
[0.001 - 10
*
s]
This parameter cannot be adjusted
while the motor is running.
Enter the filter time constant. This
constant is a first-order digital low-pass
filter time for suppressing electrical noise
in terminal X30/12. A high value improves
dampening, but also increases the delay
through the filter.
AN-47 Term. X30/12 Live Zero
Option:
Function:
This parameter makes it possible to disable the
live zero monitoring. For example, this is used if
the analog outputs are used as part of a
decentral I/O system (for example when not part
of any control functions related to the frequency
converter, but feeding an external control system
with data).
[0]
Disabled
[1]
Enabled
*
3.8.6 AN-5# Analog Output 42
Parameters to configure the scaling and limits for Analog
Output 1 (terminal 42)
AN-50 Terminal 42 Output
Option:
Function:
Select the function of terminal 42 as an
analog current output. Depending on the
selection the output is either a 0–20 mA or
4–20 mA output. The current value can be
read out in the keypad in
parameter DR-65 Analog Output 42 [mA].
[0]
No
Indicates no signal on the analog output.
*
operation
DET-618D
AF-650 GP™ Programming Guide
AN-50 Terminal 42 Output
Option:
[100] Output
frequency
[101] Reference
[102] Feedback
[103] Motor
Current
[104] Torque rel
to limit
[105] Torq relate
to rated
[106] Power
[107] Speed
[108] Torque
[109] Max Out
Freq
[113] PID
Clamped
Output
[117] Shaft Power
[118] Shaft Power
4-20mA
[119] Torque %
lim
[130] Output freq.
4-20mA
02/2016 All rights reserved.
Function:
0 Hz = 0 mA; 100 Hz = 20 mA.
Parameter F-50 Reference Range [Min - Max]
0% = 0 mA; 100% = 20 mA
Parameter F-50 Reference Range [-Max - Max]
-100% = 0 mA; 0% = 10 mA; +100% = 20
mA
Parameter F-50 Reference Range [Min - Max]
0% = 0mA; 100% = 20mA
Parameter F-50 Reference Range [-Max - Max]
-100% = 0 mA; 0% = 10 mA; +100% = 20
mA
The value is taken from
parameter DR-37 Drive Max. Current. The
inverter maximum current (160% current) is
equal to 20 mA.
Example: Inverter normal current (11 kW) is
24 A. 160 %=38.4 A. Motor normal current is
22 A, the readout is 11.46 mA.
20 mA x 22 A
= 11 . 46 mA
38 . 4 A
In case the normal motor current is equal to
20 mA, the output setting of
parameter AN-52 Terminal 42 Output Max
Scale is:
I
 x 100
38 . 4 x 100
DRIVE
Max
=
= 175 %
I
22
Motor
Norm
The torque setting is related to setting in
parameter F-40 Torque Limiter (Driving)
The torque is related to the motor torque
setting.
Taken from parameter P-07 Motor Power [kW].
Taken from parameter F-53 Maximum
Reference. 20 mA equals to value in
parameter F-53 Maximum Reference.
Torque reference related to 160% torque.
0 Hz = 0 mA,parameter F-03 Max Output
Frequency 1 = 20 mA.
Torque% lim: Torque reference.
parameter F-50 Reference Range [Min - Max]
0% = 0mA; 100% = 20mA
parameter F-50 Reference Range [-Max - Max]
-100% = 0mA; 0% = 10mA; +100% = 20mA
0 Hz = 4 mA, 100 Hz = 20 mA
3
3
83