GE AF-650 GP Programming Manual page 29

General purpose drive
Hide thumbs Also See for AF-650 GP:
Table of Contents

Advertisement

Parameter Descriptions
3.2.3 K-2# Keypad Display
Define the variables displayed in the keypad.
NOTICE
3
3
Please refer to parameter K-37 Display Text 1,
parameter K-38 Display Text 2 and parameter K-39 Display
Text 3 for information on how to write display texts.
[0]
None
[953]
Profibus
Warning Word
[2205] Readout
Transmit Error
Counter
[2206] Readout Receive
Error Counter
[2207] Readout Bus Off
Counter
[2213] Warning
Parameter
[1501] Running Hours
[1502] kWh Counter
[1200] Control Word
[1201] Reference [Unit]
[1202] Reference %
[1203] Status Word
[1205] Main Actual
Value [%]
[1209] Custom Readout
[1210] Power [kW]
[1211] Power [hp]
[1212] Motor Voltage
[1213] Frequency
[1214] Motor Current
[1215] Frequency [%]
[1216] Torque
[1217] Speed [RPM]
28
Select a variable for display in line 1,
left position. The options are the same
as listed for parameter group K-2#.
No display value selected.
Present control word
Total reference (sum of digital/analog/
preset/bus/freeze ref./catch up and
slow-down) in selected unit.
Total reference (sum of digital/analog/
preset/bus/freeze ref./catch up and
slow-down) in percent.
Present status word.
Actual value as a percentage.
Actual power consumed by the motor
in kW.
Actual power consumed by the motor
in HP.
Voltage supplied to the motor.
Motor frequency, i.e. the output
frequency from the frequency
converter in Hz
Phase current of the motor measured
as effective value.
Motor frequency, i.e. the output
frequency from the frequency
converter in percent.
Actual motor torque in Nm
Speed in RPM (revolutions per minute)
i.e. the motor shaft speed in closed
loop.
02/2016 All rights reserved.
[1218] Motor Thermal
Thermal load on the motor, calculated
by the Electronic Thermal Overload
function.
[1219] KTY Sensor
Temperature
[1220] Motor Angle
[1221] Phase Angle
[1222] Torque %
Present motor load as a percentage of
the rated motor torque.
[1230] DC Link Voltage
Intermediate circuit voltage in the
frequency converter.
[1232] BrakeEnergy/s
Present brake power transferred to an
external brake resistor.
Stated as an instantaneous value.
[1233] BrakeEnergy/2
Brake power transferred to an external
min
brake resistor. The mean power is
calculated continuously for the most
recent 120 seconds.
[1234] Heatsink Temp.
Present heat sink temperature of the
frequency converter. The cut-out limit
is 95 ±5 ±°C; cutting back in occurs at
70 ±5° C.
[1235] Inverter Thermal Percentage load of the inverters.
[1236] Inv. Nom.
Nominal current of the frequency
Current
converter.
[1237] Inv. Max. Current Maximum current of the frequency
converter.
[1238] Logic Controller
State of the event executed by the
State
control.
[1239] Control Card
Temperature of the control card.
Temp.
[1250] External
Sum of the external reference as a
Reference
percentage, i.e. the sum of analog/
pulse/bus.
[1251] Pulse Reference
Frequency in Hz connected to the
digital inputs (18, 19 or 32, 33).
[1252] Feedback [Unit]
Reference value from programmed
digital input(s).
[1253] Digi Pot
Reference
[1260] Digital Input
Signal states form the 6 digital
terminals (18, 19, 27, 29, 32 and 33).
Input 18 corresponds to the bit at the
far left. Signal low = 0; Signal high = 1.
[1261] Terminal 53
Setting of input terminal 54. Current =
Switch Setting
0; Voltage = 1.
[1262] Analog Input 53
Actual value at input 53 either as a
reference or protection value.
[1263] Terminal 54
Setting of input terminal 54. Current =
Switch Setting
0; Voltage = 1.
[1264] Analog Input 54
Actual value at input 54 either as
reference or protection value.
[1265] Analog Output
Actual value at output 42 in mA. Use
42 [mA]
parameter AN-50 Terminal 42 Output to
select the value to be shown.
DET-618D

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents