Recycling - Daikin R-32 rooftop Series Operation Manual

Rooftop packaged unit
Table of Contents

Advertisement

5.8.5

Recycling

Full air recycling at system start-up or after a washing cycle is intended to achieve the temperature and humidity
setpoints more quickly.
If air recycling only is required at unit start-up, parameter "DA52" must be set to "2".
If parameter "DA52" is set to "3", a washing cycle is performed before recycling.
While recycling is in progress, the controller keeps the exhaust air and external air dampers closed and it keeps the
recycled air damper open for the time setpoint stored in parameter "DA55".
If the value in parameter "DA53" is set to "0", the washing cycle takes place without any thermoregulation of the air.
If the value in parameter "DA53" is set to "1", thermoregulation is active.
While recycling is in progress, a button flashes on the main screen which is pressed to stop the cycle manually before
the time set in parameter "DA55" elapses.
We reserve the right to make changes without any prior notice.
Translation from original instructions
UATYA
Packaged Rooftop
33
4P645203-1