Carrier WeatherMaker 48TC Series Installation Instructions Manual page 51

Single package rooftop with gas heat/electric cooling
Hide thumbs Also See for WeatherMaker 48TC Series:
Table of Contents

Advertisement

Table 19 — Dry Bulb Operation with DCV (CO
DEMAND
OUTSIDE AIR
CONTROLLED
GOOD TO
VENTILATION (DCV)
ECONOMIZE
Below CO
Set
2
Above CO
Set
2
*With stage 3 delay (STG3 DLY) in Advanced setup menu can turn on second stage of mechanical cooling Y2-O after the delay if the call for Y1-I and Y2-I
have not been satisfied.
Table 20 — Enthalpy Operation without DCV (CO
DEMAND
OUTSIDE AIR
CONTROLLED
GOOD TO
VENTILATION (DCV)
ECONOMIZE
NO CO
SENSOR
2
*With stage 3 delay (STG3 DLY) in Advanced setup menu can turn on second stage of mechanical cooling Y2-O after the delay if the call for Y1-I and Y2-I
have not been satisfied.
Table 21 — Enthalpy Operation with DCV (CO
DEMAND
OUTSIDE AIR
CONTROLLED
GOOD TO
VENTILATION (DCV)
ECONOMIZE
Below CO
Set
2
Above CO
Set
2
*With stage 3 delay (STG3 DLY) in Advanced setup menu can turn on second stage of mechanical cooling Y2-O after the delay if the call for Y1-I and Y2-I
have not been satisfied.
Y1-I
Y2-I
OFF
OFF
No
ON
OFF
ON
ON
OFF
OFF
ON
OFF
Yes
ON
ON
OFF
OFF
No
ON
OFF
ON
ON
OFF
OFF
Yes
ON
OFF
ON
ON
Y1-I
Y2-I
OFF
OFF
NO
ON
OFF
ON
ON
OFF
OFF
YES
ON
OFF
ON
ON
Y1-I
Y2-I
OFF
OFF
No
ON
OFF
ON
ON
OFF
OFF
ON
OFF
Yes
ON
ON
OFF
OFF
No
ON
OFF
ON
ON
OFF
OFF
Yes
ON
OFF
ON
ON
Sensor) — 2 Speed Fan
2
FAN
Y1-O
Y2-O
SPEED
LOW
0v/Off
0v/Off
LOW
24v/On
0v/Off
HIGH
24v/On
24v/On
LOW
0v/Off
0v/Off
LOW
0v/Off
0v/Off
HIGH
24v/On
0v/Off
LOW
0v/Off
0v/Off
LOW
24v/On
0v/Off
HIGH
24v/On
24v/On
LOW
0v/Off
0v/Off
LOW
0v/Off
0v/Off
HIGH
24v/On
0v/Off*
Sensor) — 2 Speed Fan
2
FAN
Y1-O
Y2-O
SPEED
LOW
0v/Off
0v/Off
LOW
24v/On
0v/Off
HIGH
24v/On
24v/On
LOW
0v/Off
0v/Off
LOW
0v/Off
0v/Off
HIGH
24v/On
0v/Off*
Sensor) — 2 Speed Fan
2
FAN
Y1-O
Y2-O
SPEED
LOW
0v/Off
0v/Off
LOW
24v/On
0v/Off
HIGH
24v/On
24v/On
LOW
0v/Off
0v/Off
LOW
0v/Off
0v/Off
HIGH
24v/On
0v/Off
LOW
0v/Off
0v/Off
LOW
24v/On
0v/Off
HIGH
24v/On
24v/On
LOW
0v/Off
0v/Off
LOW
0v/Off
0v/Off
HIGH
24v/On
0v/Off*
51
OCCUPIED
UNOCCUPIED
VENTMIN
VENTMIN
VENTMIN
VENTMIN
VENTMIN to
Closed to Full-Open
Full-Open
VENTMIN to
Closed to Full-Open
Full-Open
VENTMIN to
VENTMAX
VENTMIN to
VENTMAX
VENTMIN to
VENTMAX
VENTMIN to
VENTMAX
VENTMIN to
Closed to Full-Open
Full-Open
VENTMIN to
Closed to Full-Open
Full-Open
OCCUPIED
UNOCCUPIED
MIN POS
MIN POS
MIN POS
MIN POS
MIN POS to Full Open
Closed to Full-Open
MIN POS to Full Open
Closed to Full-Open
OCCUPIED
UNOCCUPIED
VENTMIN
VENTMIN
VENTMIN
VENTMIN
VENTMIN to
Closed to Full-Open
Full-Open
VENTMIN to
Closed to Full-Open
Full-Open
VENTMIN to
VENTMAX
VENTMIN to
VENTMAX
VENTMIN to
VENTMAX
VENTMIN to
VENTMAX
VENTMIN to
Closed to Full-Open
Full-Open
VENTMIN to
Closed to Full-Open
Full-Open
Closed
Closed
Closed
Closed
Closed
Closed
Closed
Closed
Closed
Closed
Closed
Closed
Closed
Closed
Closed
Closed
Closed
Closed
Closed
Closed

Hide quick links:

Advertisement

Table of Contents

Troubleshooting

loading

Table of Contents