Netbay Rack Power Distribution Units - IBM NetBAY25 Planning Manual

Table of Contents

Advertisement

NetBAY rack power distribution units

The following tables contain product specifications for the NetBAY Rack PDU, NetBAY
Server PDU, and NetBAY Front-end PDU:
Table 2. NetBAY Rack PDU specifications.
Table 3. NetBAY Server PDU specifications.
30
IBM NetBAY Rack: Planning Guide
Height
Width
Depth
Weight
Operating temperature at 0–914 m
(0–3000 ft)
Operating temperature at 914–2133 m
(3000–7000 ft)
Operating humidity (non-condensing) 8% – 80%
Rated voltage
Rated frequency
Maximum power rating
Circuit breaker
Power inlet
Power outlets
Height
Width
Depth
Weight
Operating temperature at 0–914 m
(0–3000 ft)
Operating temperature at 914–2133 m
(3000–7000 ft)
Operating humidity (non-condensing) 8% – 80%
Rated voltage
Rated frequency
Maximum power rating
Power inlet
Transfer time
Power outlets
43 mm (1.7 in.)
192 mm (7.5 in.)
221 mm (8.7 in.)
1.5 kg (3.2 lb)
10° – 35°C (50° – 95°F)
10° – 32°C (50° – 90°F)
100 – 240 V ac, 15 A, single-phase
50 – 60 Hz
3600 VA
Two-pole, 15 A with time-delay protection for up to
600 A input current without nuisance tripping.
IEC 320-C20 inlet rated at 16 A (VDE) /
20 A (UL/CSA)
Seven IEC 320-C13 outlets rated at 10 A (VDE) /
15 A (UL/CSA)
43 mm (1.7 in.)
192 mm (7.5 in.)
221 mm (8.7 in.)
2.4 kg (5.4 lb)
10° – 35°C (50° – 95°F)
10° – 32°C (50° – 90°F)
100 – 127 V ac, 15 A, single-phase
200 – 240 V ac, 10 A, single-phase
50 – 60 Hz
2400 VA
Two IEC 320-C20 inlets rated at 16 A (VDE) /
20 A (UL/CSA)
< 35 ms from main to backup power
Four IEC 320-C13 outlets rated at 10 A (VDE) /
15 A (UL/CSA)

Advertisement

Table of Contents
loading

This manual is also suitable for:

Netbay42Netbay42 enterprise

Table of Contents